| Plan Review Notes For Permit 11070608 |
| Permit Number |
11070608 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-07-28 12:56:39 | 308 CLEMATIS STREET | | | PERMIT #11070608 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | *****PROVISO***** | | | | | | ALL DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS | | | OF NFPA 241. WASTE TO BE REMOVED THE SITE DAILY. | | | | | | FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING | | | DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A | | | FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN | | | 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE | | | PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST | | | BE APPROVED AND SUBMITTED IN WRITING TO THE OFFICE OF | | | THE FIRE MARSHAL. | | | | | | NO ADDRESS PROVIDED ON LIFE SAFETY SHEET. | | | | | | INSUFFICIENT FIRE ALARM DEVICES (PULL STATIONS, | | | HORN/STROBES) SHOWN ON PLAN. | | | | | | WESLEY JOLIN | | | WEST PALM BEACH FIRE RESCUE | | | FIRE & LIFE SAFETY PLAN REVIEW | | | |
|