2011-07-25 16:42:42RE-ROOF BUILDING REVIEW CHECKLIST.
 2007 FBC WITH 2009 REVISIONS.
  
 1- ACCORDING TO FBC 2009 REVISIONS SEC. 1609.4.3 THIS
 BUILDING IS LOCATED ON EXPOSURE "C". ROOF COVER
 ASSEMBLY W-32 MARKED ON FLORIDA PRODUCT APPROVAL
 SUBMITTED IS GOOD FOR A DESIGN PRESSURE OF -90.0PSF.
 CORNER DESIGN PRESSURES FOR THIS BUILDING ARE HIGHER
 THAN -90.0 PSF. NEED TO SELECT ANOTHER ASSEMBLY THAT
 MEETS THE CORNER DESIGN PRESSURES REQUIRED BY SEC. 1609
 FBC 2007.
  
 2- PROVIDE CURRENT FLORIDA PRODUCT APPROVAL FL1654-R9.
 ONE SUBMITTED IS THE OLD REVISION FL1654-R8.
  