Plan Review Notes
Plan Review Notes For Permit 11070579
Permit Number 11070579
Review Stop Z
Sequence Number 1
Notes
Date Text
2011-08-01 08:31:57FAILED
  
 1) DUE TO THE INSTALLATION OF EXTERIOR A/C EQUIPMENT
 AND A PAD, PLEASE PROVIDE A RECENT SURVEY, LESS THAN
 ONE YEAR OLD, WITH THE SETBACK DIMENSIONS TO THE EAST
 AND WEST PROPERTY LINES.
  
 2) THE SURVEY SHALL SHOW THE DIMENSIONS OF THE A/C PAD
 AND THE DISTANCE OF THE PAD TO THE EAST PROPERTY LINE.
 PLEASE NOTE THAT PURSUANT TO SECTION 94-305(B)(4) OF
 THE ZLDR: MECHANICAL EQUIPMENT MAY NOT PROJECT MORE
 THAN 4 FEET INTO A REQUIRED SETBACK.
  
 3) THE VALUE OF THE CONSTRUCTION ($35,000) EXCEEDS 50%
 OF THE STRUCTURE'S VALUE ($40,160) ACCORDING TO THE
 P.B.C. PROPERTY APPRAISER'S OFFICE; THEREFORE, PURSUANT
 TO SECTION 94-441(C)(2) OF THE ZONING AND LAND
 DEVELOPMENT REGULATIONS (ZLDR), THE LANDSCAPE ON THE
 SITE SHALL BE IN COMPLIANCE WITH ALL APPLICABLE
 REGULATIONS FOUND IN ARTICLE XIV OF THE ZLDR. IF THE
 SITE CONFORMS TO ARTICLE XIV, THEN TWO (2) COPIES OF A
 LANDSCAPE PLAN DEMONSTRATING COMPLIANCE SHALL BE
 INCLUDED WITH THE PERMIT RE-SUBMITTAL. IF THE SITE DOES
 NOT CONFORM TO ARTICLE XIV, THEN PRIOR TO THE ZONING
 APPROVAL OF THIS PERMIT A SEPARATE LANDSCAPE PERMIT AND
 IRRIGATION PERMIT SHALL BE SUBMITTED SHOWING MATERIAL
 TO BRING THE SITE INTO CONFORMITY.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.