| Plan Review Notes For Permit 11070562 |
| Permit Number |
11070562 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2011-08-03 15:54:05 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2007 | | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | | | 1. REVISE EXPOSURE CATEGORY OR EXPLAIN RATIONALE FOR | | | EXPOSURE B. FBC1609, FBC R301.2.1.4. NOTE THAT THE CODE | | | CHANGED EFFECTIVE MARCH 1, 2009. RESUB SHEET STATES | | | THAT PRESSURES WERE CHANGED. PRESSURES ARE TOO LOW, | | | MINIMUM -46.2 FOR ZONE 4. | | | | | | 2. SEE OPENING C, 123 1/4" SPAN STATED. THIS DOES NOT | | | CORRELATE WITH THE HEIGHT. IF THIS IS THE SPAN, SEE | | | SHEET 11 OF THE PRODUCT APPROVAL. 5" SPACING REQUIRED. | | | | | | 3. TIM ELLIS HAS SIGNED THE PERMIT APPLICATION WHERE | | | THE QUALIFIER'S SIGNATURE SHOULD BE. IT IS NOT CLEAR | | | WHY THIS PERSON HAS REPRESENTED HIMSELF AS THE | | | QUALIFIER. PROVIDE A NEW PROPERLY NOTARIZED PERMIT | | | APPLICATION, NO WHITE OUT PERMITTED IN THE NOTARIZED | | | SIGNATURE AREA. | | | | | | 4. PRIOR TO RESUBMITTAL, HAVE THE QUALIFIER REVIEW THE | | | INSTALLATION SCHEDULE AND PROPOSED DESIGN PRESSURES FOR | | | CODE COMPLIANCE. | | | | | | | | | | | | | | | | | | |
|