| Notes |
| Date |
Text |
| 2011-07-26 10:24:03 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2007 | | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | | | 1. REVISE PRESSURES TO EXPOSURE C OR PROVIDE ENGINEERED | | | RATIONAL ANALYSIS FOR USE OF REDUCED PRESSURES, SEE | | | ASCE7-05 AND FBC R301.2.1.4. | | | | | | 2. SEE SHEET 11 OF THE PRODUCT APPROVAL. 9" SPACING | | | DOES NOT COMPLY. PLEASE ALSO CLARIFY WHICH TAPCON IS | | | PROPOSED. INSTALLATION SCHEDULE SPECIFIES "ITW TAPCON" | | | BUT SHEET 11 HAS TWO, ITW TAPCON 1/4" AND ITW BULIDEX | | | 5/8". | | | | | | |
|