| Plan Review Notes For Permit 11070543 |
| Permit Number |
11070543 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-07-22 16:36:58 | 1 NORTH CLEMATIS STREET, 4TH FLOOR | | | PERMIT #11070543 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | PLANS AND HYDRAULIC CALCULATIONS INDICATE A REMOTE AREA | | | OF 1500 SQUARE FEET BUT ONLY SEVEN SPRINKLERS AND | | | ROUGHLY 800 SQUARE FEET HAVE BEEN HYDRAULICALLY | | | CALCULATED. | | | | | | PER NFPA 13 THE HYDRAULIC AREA SHALL BE MEASURED | | | PARALLEL TO THE BRANCH LINES. | | | | | | HYDRAULIC CALCULATIONS DO NOT ACCOUNT FOR THE | | | ADDITIONAL FRICTION LOSS ASSOCIATED WITH THE FLEXIBLE | | | DROPS SUPPLYING SPRINKLERS. | | | | | | INDICATE ON THE PLANS THE MAXIMUM LENGTH OF FLEXIBLE | | | DROPS TO BE USED, THE MINIMUM BENDING RADIUS AND THE | | | MAXIMUM NUMBER OF BENDS PERMITTED PER THE LISTING | | | REQUIREMENTS. | | | | | | FOR SYSTEM PRESSURES EXCEEDING 100 PSI, THE HARD PIPED | | | SPRINKLERS SHALL BE PROTECTED FROM UPWARD MOVEMENT. | | | INDICATE THE METHOD FOR RESTRAINING UPWARD MOVEMENT AND | | | ADJUST PIPE HANGER LOCATION SCHEDULE AND ARMOVER DETAIL | | | FOR 100 PSI. | | | | | | THE REQUIRED RESIDUAL PRESSURE SHOWN ON THE PLANS IS A | | | NEGATIVE NUMBER. | | | | | | PROVIDE A FLOOR DESIGNATION IN THE TITLE BLOCK OR ON | | | THE PLANS. | | | | | | NOTE: ONLY THE BRAIDED FLEXIBLE HOSE ASSEMBLIES ARE | | | ACCEPTED BY THE OFFICE OF THE FIRE MARSHAL. | | | | | | WESLEY JOLIN | | | WEST PALM BEACH FIRE RESCUE | | | FIRE & LIFE SAFETY PLAN REVIEW |
|