| Plan Review Notes For Permit 11070495 |
| Permit Number |
11070495 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-07-29 14:41:12 | FBC PLUMBING 2007 REVIEW #1 | | | DENIED: | | | | | | 1A. SHEET #3 SHOWS A FIXTURES BEING MOVED AND DELETED. | | | 106.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. | | | PLUMBING (3). WATER SUPPLY PIPING AND (13) SANITARY | | | PLUMBING RISER WILL BE REQUIRED. | | | | | | 1B. PLEASE INCLUDE OCCUPANT LOAD AND OCCUPANCY TYPE ON | | | PLAN. WITH FIXTURES BEING REMOVED, MINIMUN REQUIRED | | | FIXTURES NEED TO BE CONCIDERED. | | | SECTION 403 | | | MINIMUM PLUMBING FACILITIES | | | | | | REVIEW BY | | | LARRY WAGNER | | | CHIEF PLUMBING INSPECTOR | | | PHONE # 805-6692 | | | EMAIL [email protected] | | | FAX # 805-6676 | | | |
|