Plan Review Notes
Plan Review Notes For Permit 11070466
Permit Number 11070466
Review Stop B
Sequence Number 1
Notes
Date Text
2011-08-02 08:04:53REVISION DENIED BY BUILDING
  
 1) THE FLOOR TRUSS PLACEMENT PLAN AND TRUSS DRAWINGS
 FROM THE TRUSS COMPANY ARE NOT SIGNED AND SEALED BY THE
 TRUSS SYSTEM ENGINEER AS REQUIRED BY FAC 61G15-31.003.
  
 2) SHEET S-1 SHOWS A 4" STEP DOWN FROM THE KITCHEN AREA
 TO THE LAUNDRY ROOM. THIS IS NOT REFLECTED ON THE FLOOR
 PLAN ON SHEET A-1.1 OR THE TRUSS DRAWINGS. PLEASE
 CORRECT.
  
 3) SHEET S-1 SHOWS A 2-1/2" STEP AT THE REAR OF THE
 GARAGE WHICH IS NOT SHOWN ON SECTION 10 ON S-3. PLEASE
 CORRECT.
  
 4) SHOW COMPLIANCE WITH FBC R319.1(1) WHICH REQUIRES
 PROTECTION AGAINST DECAY OF FLOOR JOISTS OR THE BOTTOM
 OF A WOOD STRUCTURAL FLOOR WHEN CLOSER THAN 18 INCHES
 OR WOOD GIRDERS WHEN CLOSER THAN 12 INCHES TO THE
 EXPOSED GROUND IN CRAWL SPACES.
  
 5) SPECIFY THE UNDER FLOOR INSULATION THAT WILL BE
 INSTALLED IN THE CRAWL SPACE AND SUBMIT TWO COPIES OF
 REVISED ENERGY CALCULATIONS AS REQUIRED BY FBC 11 SECT.
 N1100.
  
 6) THE SURFACE WATER DRAINAGE PLAN ON SHEET A-0.1 DOES
 NOT INDICATE HOW THE SURFACE DRAINAGE WILL BE DIVERTED
 TO A STORM SEWER CONVEYANCE OR OTHER APPROVED POINT OF
 COLLECTION AS REQUIRED BY FBC R401.3. PLEASE CORRECT.
  
 7) PROVIDE A RESPONSE LETTER INDICATING HOW THE REVIEW
 COMMENTS HAVE BEEN ADDRESSED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]