| Plan Review Notes For Permit 11070466 |
| Permit Number |
11070466 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-08-02 08:04:53 | REVISION DENIED BY BUILDING | | | | | | 1) THE FLOOR TRUSS PLACEMENT PLAN AND TRUSS DRAWINGS | | | FROM THE TRUSS COMPANY ARE NOT SIGNED AND SEALED BY THE | | | TRUSS SYSTEM ENGINEER AS REQUIRED BY FAC 61G15-31.003. | | | | | | 2) SHEET S-1 SHOWS A 4" STEP DOWN FROM THE KITCHEN AREA | | | TO THE LAUNDRY ROOM. THIS IS NOT REFLECTED ON THE FLOOR | | | PLAN ON SHEET A-1.1 OR THE TRUSS DRAWINGS. PLEASE | | | CORRECT. | | | | | | 3) SHEET S-1 SHOWS A 2-1/2" STEP AT THE REAR OF THE | | | GARAGE WHICH IS NOT SHOWN ON SECTION 10 ON S-3. PLEASE | | | CORRECT. | | | | | | 4) SHOW COMPLIANCE WITH FBC R319.1(1) WHICH REQUIRES | | | PROTECTION AGAINST DECAY OF FLOOR JOISTS OR THE BOTTOM | | | OF A WOOD STRUCTURAL FLOOR WHEN CLOSER THAN 18 INCHES | | | OR WOOD GIRDERS WHEN CLOSER THAN 12 INCHES TO THE | | | EXPOSED GROUND IN CRAWL SPACES. | | | | | | 5) SPECIFY THE UNDER FLOOR INSULATION THAT WILL BE | | | INSTALLED IN THE CRAWL SPACE AND SUBMIT TWO COPIES OF | | | REVISED ENERGY CALCULATIONS AS REQUIRED BY FBC 11 SECT. | | | N1100. | | | | | | 6) THE SURFACE WATER DRAINAGE PLAN ON SHEET A-0.1 DOES | | | NOT INDICATE HOW THE SURFACE DRAINAGE WILL BE DIVERTED | | | TO A STORM SEWER CONVEYANCE OR OTHER APPROVED POINT OF | | | COLLECTION AS REQUIRED BY FBC R401.3. PLEASE CORRECT. | | | | | | 7) PROVIDE A RESPONSE LETTER INDICATING HOW THE REVIEW | | | COMMENTS HAVE BEEN ADDRESSED. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|