| Plan Review Notes For Permit 11070424 |
| Permit Number |
11070424 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-07-27 14:31:12 | PLEASE SUBMIT AN ELECTRICAL FLOOR PLAN SHOWING THE | | | REQUIRED RECEPTACLES WITH AFCI PROTECTION, GFCI | | | PROTECTION AND TAMPER RESISTANT AS APPROPRIATE FOR THE | | | INTENDED USE. RECEPTACLES SHALL BE SPACED SO THAT AT NO | | | POINT ALONG THE FLOOR IN ANY WALL IS MORE THAN 6 FEET | | | FROM A RECEPTACLE OUTLET. THE NEW LIVING AREA REQUIRES | | | A SWITCHED RECEPTACLE OR LIGHT AND A SWITCHED LIGHT AT | | | OUTSIDE ENTRANCES. AT LEAST ONE GFCI PROTECTED | | | RECEPTACLE IS REQUIRED OUTSIDE AT THE FRONT AND REAR OF | | | THE RESIDENCE. | | | | | | PROVIDE A ONE LINE ELECTRICAL SERVICE RISER DIAGRAM | | | SHOWING THE SIZE OF THE EXISTING ELECTRIC SERVICE. SHOW | | | LOCATION OF EXISTING ELECTRICAL PANEL. | | | | | | REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO | | | INCLUDE INTERCONNECTED SMOKE DETECTORS IF THEY DO NOT | | | ALREADY EXIST WITHIN THE RESIDENCE. IF THE RESIDENCE | | | HAS GAS APPLIANCES, AN ATTACHED GARAGE OR A FIRE PLACE | | | A CARBON MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET | | | OF EACH ROOM USED FOR SLEEPING. | | | | | | CODE REFERENCES: | | | | | | 2008 NATIONAL ELECTRIC CODE | | | SECTIONS 210.8, 210.12, 210.52, 210.70, 215.5, 406.11 | | | | | | 2007 FLORIDA RESIDENTIAL BUILDING CODE | | | SECTION R313 | | | | | | | | | ROBERT LECKY | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | | | | |
|