Plan Review Notes
Plan Review Notes For Permit 11070424
Permit Number 11070424
Review Stop B
Sequence Number 1
Notes
Date Text
2011-07-25 11:38:12BUILDING PLAN REVIEW
 PERMIT: 11070424
 ADD: 8628 PLUM CAY
 CONT: O/B BOYCHUK, PATRICIA
 TEL: (561)714-0686
  
 2007 FLORIDA BUILDING CODE RESIDENTIAL W/ 2009 FBC
 SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PLEASE SEE SURVEY THIS BUILDING IS LOCATED WITHIN A
 A0 FLOOD ZONE, THE FINISH FLOOR OF THE SUN ROOM IS TO
 BE THE SAME HEIGHT AS THE FLOOR LEVEL OF 21.42 FEET
 NGVD. SECTION 94-546 WEST PALM BEACH MUNI CODE & R
 323.1. PLEASE BE AWARE THIS MAY CHANGE YOUR BUILDING
 DESIGN OF CURB.
  
 2) THE DESIGNER OF RECORD FOR THE PLANS SHALL PRINT AND
 SIGN THERE NAME ON ALL PRINTS TAKING OWNERSHIP OF
 PLANS. 106.1 ADMINISTRATIVE CODE.
  
 3) THE DESIGNER OF RECORD WILL NEED TO INDICATE TO
 WHICH WIND DESIN CRITERIA THE SUNROOM WAS DESIGNED?
 2007/09 FBC-R 301.2.1.1.
  
 4) 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL-FORCE-RESISTING SYSTEM OF THE
 BUILDING:
 4.1. BASIC WIND SPEED (3-SECOND GUST), MILES PER HOUR
 (KM/HR).
  
 4.2. WIND IMPORTANCE FACTOR, I W , AND BUILDING
 CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1, ASCE 7
 AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE 7.
  
 4.3. WIND EXPOSURE, IF MORE THAN ONE WIND EXPOSURE IS
 UTILIZED, THE WIND EXPOSURE AND APPLICABLE WIND
 DIRECTION SHALL BE INDICATED.
  
 4.4. THE APPLICABLE ENCLOSURE CLASSIFICATIONS AND, IF
 DESIGNING WITH ASCE 7, INTERNAL PRESSURE COEFFICIENT.
  
 4.5. COMPONENTS AND CLADDING. THE DESIGN WIND PRESSURES
 IN TERMS OF PSF (KN/M 2 ) TO BE USED FOR THE SELECTION
 OF EXTERIOR COMPONENTS AND CLADDING MATERIALS NOT
 SPECIFICALLY DESIGNED BY THE REGISTERED DESIGN
 PROFESSIONAL.
  
 5) 1604.4 EVERY STRUCTURE SHALL BE DESIGNED TO RESIST
 THE OVERTURNING EFFECTS CAUSED BY LATERAL FORCES
 SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND.
 THERE APPEARS TO BE A DISCREPANCY BETWEEN THE CUT
 SECTION OF PLANS AND WOOD STUD INFILL DETAILS. PLEASE
 NOTE THE CUT SECTION INDICATES A EXISTING DOUBLE
 2X BUILT UP WOOD BEAM WHERE AS THE WOOD STUD INFILL
 DETAIL INDICATES THERE TO BE A CONCRETE BEAM WITH 4
 INCH POWER CONCRETE SCREWS, PLEASE CLARIFY.
 THIS WALL WILL BECOME PART OF THE MAIN WIND FORCE
 RESISTING SYSTEM AND WILL NEED TO SHOW STRAPPING FROM
 THE WOOD INFILL WALL TO THE BEAM ABOVE.
 R601.2 A CONTINIOUS LOAD PATH BETWEEN FOUNDATIONS,
 WALLS AND ROOFS SHALL BE PROVIDED.
  
 6) PLEASE PROVIDE COMPLIANCE WITH 2007/09 FBC-R SECTION
 301.2.1.1.2. PROVIDE TO WHAT CATEGORY THIS SUN ROOM WAS
 DESIGNED.
  
 7) DEPENDING ON THE RESULTS OF COMMENT# SIX THE PRODUCT
 APPROVAL FOR T.M. WINDOWS 747 HP SINGLE HUNG WINDOWS
 MAY OR MAY NO BE ACCEPTED. NOTE THIS NOA (10-0202.03)
 ONLY HAS SMALL MISSILE IMPACT TESTING, PLEASE REVIEW
 2007/09 FBC-R R 301.2.1.2.
  
 8) PLEASE REVIEW CUT SECTION OF WALL FOR CODE
 COMPLIANCE REQUIRING BOND BREAK: R703.6.3 WHERE CEMENT
 PLASTER (STUCCO) IS TO BE APPLIED TO LATH OVER FRAME
 CONSTRUCTION, MEASURES SHALL BE TAKEN TO PREVENT
 BONDING BETWEEN THE CEMENT PLASTER AND THE
 WATER-RESISTIVE BARRIER. A BOND BREAK SHALL BE PROVIDED
 BETWEEN THE WATER-RESISTIVE BARRIER AND THE CEMENT
 PLASTER (STUCCO) CONSISTING OF ONE OF THE FOLLOWING:
  
 8.1. TWO LAYERS OF AN APPROVED WATER-RESISTANT BARRIER
 MATERIAL; OR
  
 8.2. ONE LAYER OF AN APPROVED WATER-RESISTANT BARRIER
 OVER AN APPROVED PLASTIC HOUSE WRAP; OR
  
 8.3. OTHER APPROVED METHODS OR MATERIALS APPLIED IN
 ACCORDANCE WITH THE MANUFACTURER'S INSTALLATION
 INSTRUCTIONS.
  
 9) PLANS DO NOT PROVIDE DETAILS OF WINDOW AND DOOR
 OPENINGS 2007/09 FBC-R TABLE R502.2.5.1 SEE NOTE (NJ)
 NUMBER OF JACKS.
  
 10) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved