| Plan Review Notes For Permit 11070378 |
| Permit Number |
11070378 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-07-27 11:37:52 | REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO | | | INCLUDE INTERCONNECTED SMOKE DETECTORS. IF THE | | | RESIDENCE HAS GAS APPLIANCES, AN ATTACHED GARAGE OR A | | | FIRE PLACE A CARBON MONOXIDE DETECTOR IS REQUIRED | | | WITHIN TEN FEET OF EACH ROOM USED FOR SLEEPING. FBC | | | R313 | | | NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11 | | | | | | | | | ROBERT LECKY | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | | | | |
|