Plan Review Notes
Plan Review Notes For Permit 11070356
Permit Number 11070356
Review Stop B
Sequence Number 1
Notes
Date Text
2011-07-21 10:19:322007 FBC W/2009 REVISIONS
  
 DENIED BY BUILDING
  
 1) THE EXPOSURE CATEGORY THAT WAS USED FOR THE
 CALCULATIONS IS INCORRECT. THE STRUCTURE IS LOCATED IN
 EXPOSURE "C". SEE FBC R301.2.1.4.3.
  
 2) THE DESIGN PRESSURE CALCULATIONS WILL NEED TO BE
 CALCULATED USING EXPOSURE CATEGORY "C". THE OPENING
 PRESSURES THAT WERE SUBMITTED FOR EXPOSURE "B" ARE
 INCORRECT. IT APPEARS THAT THE WRONG TRIBUTARY AREA WAS
 USED IN THE CALCULATIONS. THE TRIBUTARY AREA OR
 EFFECTIVE WIND AREA IS THE SIZE OF THE OPENING. FBC
 R301.2.1 AND ASCE 7-05.
  
 3) THE WINDOW OPENING SCHEDULE SPECIFIES A PRODUCT
 ACCEPTANCE NUMBER OF FL7858 WHICH IS FOR A SLIDING
 GLASS DOOR. A PRODUCT APPROVAL FOR FOR A FIXED WINDOW
 FL5859 WAS SUBMITTED. PLEASE CLARIFY.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW