| Plan Review Notes For Permit 11070356 |
| Permit Number |
11070356 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-07-21 10:19:32 | 2007 FBC W/2009 REVISIONS | | | | | | DENIED BY BUILDING | | | | | | 1) THE EXPOSURE CATEGORY THAT WAS USED FOR THE | | | CALCULATIONS IS INCORRECT. THE STRUCTURE IS LOCATED IN | | | EXPOSURE "C". SEE FBC R301.2.1.4.3. | | | | | | 2) THE DESIGN PRESSURE CALCULATIONS WILL NEED TO BE | | | CALCULATED USING EXPOSURE CATEGORY "C". THE OPENING | | | PRESSURES THAT WERE SUBMITTED FOR EXPOSURE "B" ARE | | | INCORRECT. IT APPEARS THAT THE WRONG TRIBUTARY AREA WAS | | | USED IN THE CALCULATIONS. THE TRIBUTARY AREA OR | | | EFFECTIVE WIND AREA IS THE SIZE OF THE OPENING. FBC | | | R301.2.1 AND ASCE 7-05. | | | | | | 3) THE WINDOW OPENING SCHEDULE SPECIFIES A PRODUCT | | | ACCEPTANCE NUMBER OF FL7858 WHICH IS FOR A SLIDING | | | GLASS DOOR. A PRODUCT APPROVAL FOR FOR A FIXED WINDOW | | | FL5859 WAS SUBMITTED. PLEASE CLARIFY. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|