| 2011-07-20 14:17:28 | 1011 NORTH DIXIE HIGHWAY |
| | PERMIT #11070343 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | DESIGN SHALL CONFORM TO THE FLORIDA FIRE PREVENTION |
| | CODE 2007 EDITION: NFPA 1 AND NFPA 101 - 2006 EDITION |
| | WITH FLORIDA AMENDMENTS. |
| | |
| | PROVIDE A LIFE SAFETY PLAN SHOWING ALL OCCUPANT LOADS, |
| | FIRE RATED WALLS, EXIT SIGNS, EMERGENCY LIGHTING, |
| | TRAVEL DISTANCES, COMMON PATH OF TRAVEL ETC. |
| | |
| | THE BUILDING IS FUNCTIONING AS A MULTIUSE OCCUPANCY. |
| | INDICATE IF THE BUILDING IS DESIGNED FOR MIXED USE |
| | (NON-SEPARATED) OR SEPARATED USE PER SECTION 6.1.14.2.1 |
| | OF NFPA 101 FLORIDA EDITION 2006. INDICATE THE ADJACENT |
| | OCCUPANCY TYPES. |
| | |
| | INDICATE THE EGRESS ROUTES FOR THE ADJACENT TENANT |
| | SPACES THAT SHARE THE SECOND FLOOR. |
| | |
| | INDICATE ON THE PLANS IF THE REAR PATIO AND REAR STAIR |
| | ARE ENCLOSED OR OPEN. |
| | |
| | PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH |
| | EXIT SIGNS. |
| | |
| | HANDRAILS ARE REQUIRED ON BOTH SIDES OF THE STAIR. |
| | HANDRAILS SHALL BE LOCATED NOT LESS THAN 34 INCHES AND |
| | NOT MORE THAN 38 INCHES ABOVE THE SURFACE OF THE TREAD, |
| | MEASURED VERTICALLY TO THE TOP OF THE RAIL FROM THE |
| | LEADING EDGE OF THE TREAD. HANDRAIL ENDS SHALL BE |
| | RETURNED TO THE WALL OR FLOOR OR SHALL TERMINATE AT |
| | NEWEL POSTS. HANDRAIL CROSS SECTION SHALL HAVE A |
| | DIAMETER OF NOT LESS THAN 1.25 INCHES AND NOT MORE THAN |
| | 2 INCHES. |
| | |
| | THE RELEASING MECHANISM ON ALL DOORS SHALL OPEN THE |
| | DOOR WITH NOT MORE THAN ONE RELEASING OPERATION. THE |
| | RELEASING MECHANISM SHALL HAVE AN OBVIOUS METHOD OF |
| | OPERATION THAT IS READILY OPERATED UNDER ALL LIGHTING |
| | CONDITIONS. THE RELEASING DEVICE SHOULD BE CAPABLE OF |
| | BEING OPERATED WITH ONE HAND AND SHOULD NOT REQUIRE |
| | TIGHT GRASPING, TIGHT PINCHING OR TWISTING OF THE WRIST |
| | TO OPERATE PER SECTION 7.2.1.5.9 OF NFPA 101 FLORIDA |
| | EDITION 2007. |
| | |
| | PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS |
| | SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE |
| | TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL |
| | DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET. |
| | |
| | PROVIDE BUILDING ADDRESS VISIBLE FROM THE STREET. |
| | NUMBERS SHALL BE AT LEAST SIX-INCHES IN HEIGHT AND |
| | SHALL CONTRAST THE BACKGROUND (REFERENCE: SECTION |
| | 10.12.1.2 OF THE FLORIDA FIRE PREVENTION CODE - NFPA |
| | 1). |
| | |
| | STRUCTURES WITH LIGHT FRAME FLOOR/ROOF TRUSS |
| | CONSTRUCTION SHALL BE IDENTIFIED WITH A SIGN AFFIXED TO |
| | THE BUILDING. THE SIGN SHALL FEATURE A MALTESE CROSS |
| | 8-INCHES WIDE AND 8-INCHES TALL AND BE OF A BRIGHT RED |
| | REFLECTIVE COLOR AND BEAR THE APPROPRIATE LETTER R/F/RF |
| | DESIGNATION PER FLORIDA STATUTE 633.027 AND FLORIDA |
| | ADMINISTRATIVE CODE 69A-60.0081. |
| | |
| | PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY |
| | RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING |
| | NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM |
| | WWW.KNOXBOX.COM. |
| | |
| | INDICATE IF THE EXISTING FIRE SPRINKLER OR EXISTING |
| | FIRE ALARM SYSTEM IS BEING UTILIZED IN THIS SPACE. |
| | |
| | WESLEY JOLIN |
| | WEST PALM BEACH FIRE RESCUE |
| | FIRE & LIFE SAFETY PLAN REVIEW |
| | |