| 2011-07-18 16:32:02 | BUILDING PLAN REVIEW |
| | PERMIT: 11070343 |
| | ADD: 1015 N DIXIE HWY |
| | CONT: LS INVESTMENTS |
| | TEL: (561) 282-5692 |
| | |
| | 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 2007 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) THE PERMIT APPLICATION INDICATES A CHANGE OF USE |
| | FROM ROOMING HOUSE(R-1 TRANSIENT OR R-2 NON-TRANSIENT) |
| | TO A BUSINESS OCCUPANCY. THE ONE SHEET PROVIDED IS |
| | CONCEPTUAL IN NATURE, 106.1.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE |
| | OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE |
| | AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT |
| | IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| | DETERMINED BY THE BUILDING OFFICIAL (SEE ALSO SECTION |
| | 106.3.5). |
| | |
| | 106.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. THE |
| | EXAMINATION OF THE DOCUMENTS BY THE BUILDING OFFICIAL |
| | SHALL INCLUDE THE FOLLOWING MINIMUM CRITERIA AND |
| | DOCUMENTS: A FLOOR PLAN; SITE PLAN; FOUNDATION PLAN; |
| | FLOOR/ROOF FRAMING PLAN OR TRUSS LAYOUT; AND ALL |
| | EXTERIOR ELEVATIONS: |
| | 106.3.5 |
| | COMMERCIAL BUILDINGS: |
| | 2. OCCUPANCY GROUP AND SPECIAL OCCUPANCY REQUIREMENTS |
| | SHALL BE DETERMINED. |
| | 3. MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED |
| | (SEE TABLE 503). |
| | |
| | 4. FIRE-RESISTANT CONSTRUCTION REQUIREMENTS SHALL |
| | INCLUDE THE FOLLOWING COMPONENTS: |
| | FIRE-RESISTANT SEPARATIONS |
| | FIRE-RESISTANT PROTECTION FOR TYPE OF CONSTRUCTION |
| | PROTECTION OF OPENINGS AND PENETRATIONS OF RATED WALLS |
| | FIRE BLOCKING AND DRAFTSTOPPING AND CALCULATED FIRE |
| | RESISTANCE |
| | 6. LIFE SAFETY SYSTEMS SHALL BE DETERMINED AND SHALL |
| | INCLUDE THE FOLLOWING REQUIREMENTS: |
| | OCCUPANT LOAD AND EGRESS CAPACITIES |
| | 7. OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE: |
| | OCCUPANCY LOAD |
| | GROSS |
| | NET |
| | MEANS OF EGRESS |
| | EXIT ACCESS |
| | EXIT |
| | EXIT DISCHARGE |
| | STAIRS CONSTRUCTION/GEOMETRY AND PROTECTION |
| | DOORS |
| | EMERGENCY LIGHTING AND EXIT SIGNS |
| | SPECIFIC OCCUPANCY REQUIREMENTS |
| | CONSTRUCTION REQUIREMENTS |
| | HORIZONTAL EXITS/EXIT PASSAGEWAYS |
| | FIRE SPRINKLERS |
| | TENANT SEPERATION WALLS |
| | |
| | 2) CHANGE OF OCCUPANCY FOR A PORTION OF A BUILDING |
| | SHALL COMPLY WITH 2007/09 EXISTING BUILDING CODE |
| | CHAPTER 9, SECTION 901.3.1 PARTIAL CHANGE OF OCCUPANCY |
| | CLASSIFICATION. WHERE A PORTION OF AN EXISTING BUILDING |
| | IS CHANGED TO A NEW OCCUPANCY CLASSIFICATION, SECTION |
| | 912 SHALL APPLY. |
| | |
| | 1. THE DESIGNER OF RECORD WILL NEED TO DETERMINE IF |
| | THIS BUILDING HAS CHANGE OF OCCUPANCY CLASSIFICATION |
| | WITH OR WITHOUT SEPERATION. 2007 EXST BLD 912.1.1.1/ |
| | 912.1.1.2 |
| | |
| | 2. 912.1.2 FIRE PROTECTION AND INTERIOR FINISH. |
| | |
| | 3. 912.1.4 ACCESSIBILITY SHALL COMPLY WITH EXT BLD |
| | 912.8. PLEASE ALSO REVIEW 2007 FBC-B 11-4.3.11 AREA OF |
| | RESCUE ASSISTANCE. |
| | |
| | 4. EXT BLD 912.2.1 FIRE SPRINKLER SYSTEMS |
| | |
| | 5. EXT BLD 912.2.2 FIRE ALARM & DETECTION |
| | |
| | 6) EXT BLD 912.3 INTERIOR FINISHES |
| | |
| | 7) 912.4.2 MEANS OF EGRESS FOR CHANGE OF USE TO EQUAL |
| | OR LOWER HAZARD CATEGORY. WHEN A CHANGE OF OCCUPANCY |
| | CLASSIFICATION IS MADE TO AN EQUAL OR LESSER HAZARD |
| | CATEGORY (HIGHER NUMBER) AS SHOWN IN TABLE 912.4, |
| | EXISTING ELEMENTS OF THE MEANS OF EGRESS SHALL COMPLY |
| | WITH THE REQUIREMENTS OF SECTION 805 FOR THE NEW |
| | OCCUPANCY CLASSIFICATION. NEWLY CONSTRUCTED OR |
| | CONFIGURED MEANS OF EGRESS SHALL COMPLY WITH THE |
| | REQUIREMENTS OF CHAPTER 10 OF THE FLORIDA BUILDING |
| | CODE, BUILDING . |
| | |
| | EXCEPTION: ANY STAIRWAY REPLACING AN EXISTING STAIRWAY |
| | WITHIN A SPACE WHERE THE PITCH OR SLOPE CANNOT BE |
| | REDUCED BECAUSE OF EXISTING CONSTRUCTION SHALL BE |
| | PERMITTED FOR CONTINUED USE SUBJECT TO APPROVAL OF THE |
| | BUILDING CODE OFFICIAL. ALSO, SEE SECTION 1001.4 OF THE |
| | FLORIDA BUILDING CODE, BUILDING . |
| | |
| | 912.4.3 EGRESS CAPACITY. EGRESS CAPACITY SHALL MEET OR |
| | EXCEED THE OCCUPANT LOAD AS SPECIFIED IN THE FLORIDA |
| | BUILDING CODE, BUILDING , FOR THE NEW OCCUPANCY. |
| | |
| | 912.4.4 HANDRAILS. EXISTING STAIRWAYS SHALL COMPLY WITH |
| | THE HANDRAIL REQUIREMENTS OF SECTION 705.9 IN THE AREA |
| | OF THE CHANGE OF OCCUPANCY CLASSIFICATION. |
| | |
| | 912.4.5 GUARDS. EXISTING GUARDS SHALL COMPLY WITH THE |
| | REQUIREMENTS IN SECTION 705.10 IN THE AREA OF THE |
| | CHANGE OF OCCUPANCY CLASSIFICATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | 912.7 ENCLOSURE OF VERTICAL SHAFTS. ENCLOSURE OF |
| | VERTICAL SHAFTS SHALL BE IN ACCORDANCE WITH SECTIONS |
| | 912.7.1 THROUGH 912.7.4. |
| | |
| | 912.7.1 MINIMUM REQUIREMENTS. VERTICAL SHAFTS SHALL BE |
| | DESIGNED TO MEET THE FLORIDA BUILDING CODE, BUILDING |
| | REQUIREMENTS FOR ATRIUMS OR THE REQUIREMENTS OF THIS |
| | SECTION. |
| | |
| | 3) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | |
| | |
| | |
| | |
| | |