| Plan Review Notes For Permit 11070337 |
| Permit Number |
11070337 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-07-14 15:01:40 | RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW CHECKLIST. | | | 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS. | | | | | | 1- CLEARLY IDENTIFY WHICH APPROVED ASSEMBLY FROM NOA | | | 09-0820.11 IS GOING TO BE INSTALLED TO VERIFY | | | COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. R301. | | | | | | 2- PROVIDE RAS 117 CALCULATIONS FOR INSULATION | | | ATTACHMENT AS REQUIRED BY THE SELECTED APPROVED | | | ASSEMBLY. AND BY GENERAL LIMITATION #7 FOR NAIL | | | ENHANCING AT PERIMETER AND CORNER AREAS. | | | | | | ***NOTE: DESIGN PROFESSIONAL DOING THE CALCULATIONS TO | | | TAKE INTO CONSIDERATION THAT ACCORDING TO SEC. | | | R301.2.1.4.3 THIS BUILDING IS LOCATED ON EXPOSURE "C". | | | | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 |
|