| 2012-01-09 16:38:42 | RESIDENTIAL (R2) REPAIRS THIRD BUILDING REVIEW |
| | COMMENTS. |
| | 2007 FBC WITH 2009 REVISIONS. |
| | |
| | 1- ENGINEER DRAWINGS SUBMITTED ARE ONLY FOR CONDO UNIT |
| | #1 OF BUILDING A. THERE ARE 8 DIFFERENT PERMIT |
| | APPLICATIONS FOR WORK TO BE PERFORMED ON 8 DIFFERENT |
| | CONDO UNITS. PLEASE PROVIDE DRAWINGS IDENTIFYING THE |
| | SCOPE OF WORK TO BE PERFORMED ON EACH UNIT. REVISE ALL |
| | THE INFORMATION ON PLANS AS REQUIRED. SEC. 106.1.1 CITY |
| | AMENDMENTS TO FBC. |
| | |
| | *** SAME DRAWINGS WERE SUBMITTED WITHOUT IDENTIFYING |
| | ALL UNITS INVOLVED IN THESE REPAIRS. |
| | |
| | 2- PLEASE REVISE THE BUILDING CODE INFORMATION SHOWN ON |
| | SHEET C-1: THE OCCUPANCY GROUP IS R2 NOT R3. REVISE AS |
| | REQUIRED. |
| | |
| | *** ENGINEER NEEDS TO REVISE ORIGINAL DRAWINGS. PLANS |
| | SUBMITTED ARE THE SAME ONES THAT WERE SUBMITTED ON |
| | PREVIOUS REVIEW. THEY HAVE HAND WRITTEN REVISIONS NOT |
| | DONE BY THE ENGINEER RESPONSIBLE FOR THE PLANS. ALSO, |
| | PLANS SUBMITTED ARE MISSING THE ENGINEER'S SEAL AND THE |
| | SIGNATURE MUST BE ORIGINAL NOT COPY. CHAPTER 471 |
| | FLORIDA STATUTE. |
| | |
| | 3- PLEASE PROVIDE COMPLETE WALL SECTION DETAIL THRU THE |
| | BALCONY TO BE REPLACED. PROVIDE COMPLETE DETAIL/SECTION |
| | AND SPECIFICATIONS. SPECIFY ALL MATERIALS, FASTENING, |
| | WATERPROOFING, ETC. SEC. 106.1.1 CITY AMENDMENTS TO |
| | FBC. |
| | |
| | *** ENGINEER OF RECORD DIDN'T PROVIDE ANY DRAWINGS. |
| | |
| | 4- PLEASE PROVIDE COMPLETE DETAIL/SPECIFICATIONS FOR |
| | THE BALCONY GUARDRAIL TO BE REPLACED TO SHOW COMPLIANCE |
| | WITH SEC. 1013 AND SEC. 1607.7 FBC 2007. |
| | |
| | ***ENGINEER OF RECORD DIDN'T PROVIDE ANY DRAIWGNS |
| | |
| | 5- ENTRY DOOR NOA 08-1015.05 SUBMITTED DOESN'T MATCH |
| | NOA 07--0618.10 SPECIFIED BY THE ENGINEER ON SHEET A-2. |
| | REVISE AS REQUIRED TO MATCH. |
| | |
| | *** ENGINEER DIDIN'T REVISE PLANS. |
| | |
| | 6- NOTICE OF COMMENCEMENT SIGNATURE WAS CLARIFIED. |
| | |
| | 7- PLEASE UPDATE VALUATION TO INCLUDE ALL SCOPE OF WORK |
| | SHOWN ON PLANS. INCLUDE THE DOORS/WINDOWS REPLACEMENT, |
| | NEW DECK AND GUARDRAIL AND PROFESSIONAL ENGINEER FEES |
| | AS REQUIRED BY SEC. 108.3 CITY AMENDMENTS TO FBC. |
| | PERMIT TYPE AND FEES TO BE ADJUSTED ACCORDINGLY. |
| | |
| | *** VALUATION WAS NOT UPDATED. |
| | |