| 2011-11-29 15:49:46 | RESIDENTIAL (R2) REPAIRS BUILDING REVIEW COMMENTS. |
| | 2007 FBC WITH 2009 REVISIONS. |
| | |
| | 1- ENGINEER DRAWINGS SUBMITTED ARE ONLY FOR CONDO UNIT |
| | #1 OF BUILDING A. THERE ARE 8 DIFFERENT PERMIT |
| | APPLICATIONS FOR WORK TO BE PERFORMED ON 8 DIFFERENT |
| | CONDO UNITS. PLEASE PROVIDE DRAWINGS IDENTIFYING THE |
| | SCOPE OF WORK TO BE PERFORMED ON EACH UNIT. REVISE ALL |
| | THE INFORMATION ON PLANS AS REQUIRED. SEC. 106.1.1 CITY |
| | AMENDMENTS TO FBC. |
| | |
| | 2- PLEASE REVISE THE BUILDING CODE INFORMATION SHOWN ON |
| | SHEET C-1: THE OCCUPANCY GROUP IS R2 NOT R3. REVISE AS |
| | REQUIRED. |
| | |
| | 3- PLEASE PROVIDE COMPLETE WALL SECTION DETAIL THRU THE |
| | BALCONY TO BE REPLACED. PROVIDE COMPLETE DETAIL/SECTION |
| | AND SPECIFICATIONS. SPECIFY ALL MATERIALS, FASTENING, |
| | WATERPROOFING, ETC. SEC. 106.1.1 CITY AMENDMENTS TO FBC |
| | |
| | 4- PLEASE PROVIDE COMPLETE DETAIL/SPECIFICATIONS FOR |
| | THE BALCONY GUARDRAIL TO BE REPLACED TO SHOW COMPLIANCE |
| | WITH SEC. 1013 AND SEC. 1607.7 FBC 2007. |
| | |
| | 5- ENTRY DOOR NOA 08-1015.05 SUBMITTED DOESN'T MATCH |
| | NOA 07--0618.10 SPECIFIED BY THE ENGINEER ON SHEET A-2. |
| | REVISE AS REQUIRED TO MATCH. |
| | |
| | 6- PLEASE CLARIFY IF THE CONTRACTOR IS ALSO THE |
| | PRESIDENT OF THE CONDO ASSOCIATION AND IS THE ONE |
| | AUTHORIZED TO SIGN THE NOTICE OF COMMENCEMENT. PLEASE |
| | PROVIDE DOCUMENTATION. |
| | |
| | 7- PLEASE UPDATE VALUATION TO INCLUDE ALL SCOPE OF WORK |
| | SHOWN ON PLANS. INCLUDE THE DOORS/WINDOWS REPLACEMENT, |
| | NEW DECK AND GUARDRAIL AND PROFESSIONAL ENGINEER FEES |
| | AS REQUIRED BY SEC. 108.3 CITY AMENDMENTS TO FBC. |
| | PERMIT TYPE AND FEES TO BE ADJUSTED ACCORDINGLY |
| | |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561)805-6712 |