| Plan Review Notes For Permit 11070315 |
| Permit Number |
11070315 |
|
| Review Stop |
B |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2012-01-25 16:20:43 | RESIDENTIAL (R2) REPAIRS FOURTH BUILDING REVIEW | | | CHECKLIST. | | | 2007 FBC WITH 2009 REVISIONS. | | | | | | 1- PLEASE PROVIDE COMPLETE WALL SECTION DETAIL THRU THE | | | BALCONY TO BE REPLACED. PROVIDE COMPLETE DETAIL/SECTION | | | AND SPECIFICATIONS. SPECIFY ALL MATERIALS, FASTENING, | | | ETC. SEC. 106.1.1 CITY AMENDMENTS TO FBC TO VERIFY | | | COMPLIANCE WITH ALL THE DESIGN LOADS REQUIRED BY SEC. | | | 1603 FBC 2007. | | | | | | *** ENGINEER OF RECORD RESPONDED "DECKING AS SELECTED | | | BY OWNER". DECKING IS PART OF THE BALCONY ASSEMBLY. | | | ENGINEER NEEDS TO SPECIFY MATERIAL TYPE, SIZE AND | | | FASTENING METHOD TO SHOW COMPLIANCE WITH ALL THE DESIGN | | | LOADS REQUIRED BY THE CODE SECTION LISTED ABOVE. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER. | | | (561)805-6712 |
|