| 2011-07-21 13:16:06 | FBC 2007 PLUNBING REVIEW # 1 |
| | DENIED: |
| | |
| | 1. ONE SET OF PLANS THE DESIGNER OF RECORD IS A COPIED |
| | SIGNATURE AND MISSING THE ARCHITECT'S SEAL. SANDRA |
| | PUERTA, AR 95385. FL ADMINISTRATIVE RULE 61G-16.003 |
| | |
| | 2. COVER-SHEET PLUMBING FIXTURE CALULATIONS: |
| | |
| | 2A) WILL NEED TO BE BASED ON THE CORRECT BUILDING CODE |
| | CLASSIFICATION OF DAYCARE OCCUPANCY, PLUMBING FIXTURE |
| | COUNT IS BASED ON A BUSINESS OCCUPANCY. |
| | |
| | 2B) THE PLUMBING FIXTURE CALCULATIONS WILL NEED TO BE |
| | BASED ON THE CORRECTED OCCUPANCY LOAD OF 20 OCCUPANTS |
| | PER 2007/09 FBC-B TABLE 1004.1.1. INDICATE THE REQUIRED |
| | FIXTURES FOR A DAYCARE OCCUPANCY PER 2007/09 FBC-P |
| | TABLE 403.1(3) |
| | EDUCATIONAL/ DAYCARE. |
| | |
| | 3) THE FLOOR PLAN ONLY SHOWS ONE RESTROOM THAT IS |
| | ACCESSIBLE, IN REVIEWING FBC-P |
| | TABLE 403.1(3) FOR BOTH MALE AND FEMALES 1/50 FOR BOTH |
| | WATER CLOSETS AND LAVS SO TWO ACCESSIBLE RESTROOMS WILL |
| | BE REQUIRED PER 403.2. 403.2 SEPARATE FACILITIES. WHERE |
| | PLUMBING FIXTURES ARE REQUIRED, SEPARATE FACILITIES |
| | SHALL BE PROVIDED FOR EACH SEX. |
| | THE BUSINESS EXCEPTION DOES NOT MEET THE CRITERIA, NO |
| | BUSINESS OCCUPANCY WAS INDICATED ON THE PLANS. |
| | |
| | 4) PLANS ARE MISSING THE WATER SUPPLY PIPING ISOMETRIC |
| | PER 2007/09 106.5.1.3. |
| | |
| | 5) PLANS FAIL TO INDICATE COMPLIANCE WITH 2007/09 FBC-P |
| | 608.13 BACKFLOW PROTECTION. MEANS OF PROTECTION AGAINST |
| | BACKFLOW SHALL BE PROVIDED IN ACCORDANCE WITH SECTIONS |
| | 608.13.1 THROUGH 608.13.9. |
| | |
| | REVIEW BY |
| | LARRY WAGNER |
| | CHIEF PLUMBING INSPECTOR |
| | PHONE # 805-6692 |
| | EMAIL [email protected] |
| | FAX # 805-6676 |
| | |
| | |