Plan Review Notes
Plan Review Notes For Permit 11070290
Permit Number 11070290
Review Stop P
Sequence Number 1
Notes
Date Text
2011-07-21 13:16:06FBC 2007 PLUNBING REVIEW # 1
 DENIED:
  
 1. ONE SET OF PLANS THE DESIGNER OF RECORD IS A COPIED
 SIGNATURE AND MISSING THE ARCHITECT'S SEAL. SANDRA
 PUERTA, AR 95385. FL ADMINISTRATIVE RULE 61G-16.003
  
 2. COVER-SHEET PLUMBING FIXTURE CALULATIONS:
  
 2A) WILL NEED TO BE BASED ON THE CORRECT BUILDING CODE
 CLASSIFICATION OF DAYCARE OCCUPANCY, PLUMBING FIXTURE
 COUNT IS BASED ON A BUSINESS OCCUPANCY.
  
 2B) THE PLUMBING FIXTURE CALCULATIONS WILL NEED TO BE
 BASED ON THE CORRECTED OCCUPANCY LOAD OF 20 OCCUPANTS
 PER 2007/09 FBC-B TABLE 1004.1.1. INDICATE THE REQUIRED
 FIXTURES FOR A DAYCARE OCCUPANCY PER 2007/09 FBC-P
 TABLE 403.1(3)
 EDUCATIONAL/ DAYCARE.
  
 3) THE FLOOR PLAN ONLY SHOWS ONE RESTROOM THAT IS
 ACCESSIBLE, IN REVIEWING FBC-P
 TABLE 403.1(3) FOR BOTH MALE AND FEMALES 1/50 FOR BOTH
 WATER CLOSETS AND LAVS SO TWO ACCESSIBLE RESTROOMS WILL
 BE REQUIRED PER 403.2. 403.2 SEPARATE FACILITIES. WHERE
 PLUMBING FIXTURES ARE REQUIRED, SEPARATE FACILITIES
 SHALL BE PROVIDED FOR EACH SEX.
 THE BUSINESS EXCEPTION DOES NOT MEET THE CRITERIA, NO
 BUSINESS OCCUPANCY WAS INDICATED ON THE PLANS.
  
 4) PLANS ARE MISSING THE WATER SUPPLY PIPING ISOMETRIC
 PER 2007/09 106.5.1.3.
  
 5) PLANS FAIL TO INDICATE COMPLIANCE WITH 2007/09 FBC-P
 608.13 BACKFLOW PROTECTION. MEANS OF PROTECTION AGAINST
 BACKFLOW SHALL BE PROVIDED IN ACCORDANCE WITH SECTIONS
 608.13.1 THROUGH 608.13.9.
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  
  