| 2011-07-20 16:57:28 | 1120 13TH STREET |
| | PERMIT #11070290 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | PROVIDE BUILDING ADDRESS VISIBLE FROM THE STREET. |
| | NUMBERS SHALL BE AT LEAST SIX-INCHES IN HEIGHT AND |
| | SHALL CONTRAST THE BACKGROUND (REFERENCE: SECTION |
| | 10.12.1.2 OF THE FLORIDA FIRE PREVENTION CODE - NFPA |
| | 1). |
| | |
| | STRUCTURES WITH LIGHT FRAME ROOF TRUSS CONSTRUCTION |
| | SHALL BE IDENTIFIED WITH A SIGN AFFIXED TO THE |
| | BUILDING. THE SIGN SHALL FEATURE A MALTESE CROSS |
| | 8-INCHES WIDE AND 8-INCHES TALL AND BE OF A BRIGHT RED |
| | REFLECTIVE COLOR AND BEAR THE APPROPRIATE LETTER R |
| | DESIGNATION PER FLORIDA STATUTE 633.027 AND FLORIDA |
| | ADMINISTRATIVE CODE 69A-60.0081. |
| | |
| | PORTABLE FIRE EXTINGUISHERS SHALL HAVE A MINIMUM RATING |
| | OF 2A:10BC AND SHALL BE TAGGED BY A LICENSED FIRE |
| | EXTINGUISHER COMPANY. |
| | |
| | THE RELEASING MECHANISM ON ALL DOORS SHALL OPEN THE |
| | DOOR WITH NOT MORE THAN ONE RELEASING OPERATION. THE |
| | RELEASING MECHANISM SHALL HAVE AN OBVIOUS METHOD OF |
| | OPERATION THAT IS READILY OPERATED UNDER ALL LIGHTING |
| | CONDITIONS. THE RELEASING DEVICE SHOULD BE CAPABLE OF |
| | BEING OPERATED WITH ONE HAND AND SHOULD NOT REQUIRE |
| | TIGHT GRASPING, TIGHT PINCHING OR TWISTING OF THE WRIST |
| | TO OPERATE PER SECTION 7.2.1.5.9 OF NFPA 101 FLORIDA |
| | EDITION 2007. |
| | |
| | PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH |
| | EXIT SIGNS. |
| | |
| | INTERIOR WALL AND CEILING FINISH MATERIALS SHALL BE |
| | CLASS A OR CLASS B. |
| | |
| | JANITOR CLOSETS SHALL BE SEPARATED FROM THE REST OF THE |
| | BUILDING WITH A ONE-HOUR FIRE RESISTANCE RATING. |
| | |
| | EMERGENCY PLAN (EXIT LOCATIONS, EMERGENCY PHONE |
| | NUMBERS, ETC) TO BE DEVELOPED AND POSTED IN BUILDING |
| | PRIOR TO OCCUPANCY. |
| | |
| | EMERGENCY EGRESS DRILLS SHALL BE CONDUCTED MONTHLY. |
| | |
| | ARTWORK AND TEACHING MATERIALS ATTACHED TO THE WALLS |
| | SHALL NOT EXCEED 20 PERCENT OF THE INDIVIDUAL WALL |
| | AREA. |
| | |
| | FIRE PREVENTION INSPECTIONS SHALL BE CONDUCTED MONTHLY |
| | BY A TRAINED SENIOR MEMBER OF THE STAFF, AFTER WHICH A |
| | COPY OF THE LATEST INSPECTION REPORT SHALL BE POSTED IN |
| | A CONSPICUOUS PLACE IN THE DAY-CARE FACILITY. IT SHALL |
| | BE THE DUTY OF THE STAFF TO INSPECT ALL EXITS DAILY TO |
| | ENSURE THAT ALL DOORS AND EXIT PATHS ARE MAINTAINED |
| | CLEAR OF OBSTRUCTIONS. |
| | |
| | WESLEY JOLIN |
| | WEST PALM BEACH FIRE RESCUE |
| | FIRE & LIFE SAFETY PLAN REVIEW |
| | |