Plan Review Notes
Plan Review Notes For Permit 11070290
Permit Number 11070290
Review Stop E
Sequence Number 1
Notes
Date Text
2011-07-20 09:25:46PROVIDE AN ELECTRICAL PLAN. NEC 215.5
 MAXIMUM OVERCURRENT PROTECTION FOR #3 SERVICE
 CONDUCTORS AT MAIN DISCONNECT IS 100 AMPERES. NEC T.
 310.16
 ALL RECEPTACLES SHALL BE TAMPER RESISTANT. NEC 406.11
 RECEPTACLES IN BATHROOMS, KITCHEN AREAS AND OUTDOORS
 SHALL BE GFCI PROTECTED. NEC 210. 8
  
  
 ROBERT LECKY
 COMMERCIAL COMBINATION PLANS EXAMINER
 [email protected]
 561-805-6718
  