| Plan Review Notes For Permit 11070290 |
| Permit Number |
11070290 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-07-20 09:25:46 | PROVIDE AN ELECTRICAL PLAN. NEC 215.5 | | | MAXIMUM OVERCURRENT PROTECTION FOR #3 SERVICE | | | CONDUCTORS AT MAIN DISCONNECT IS 100 AMPERES. NEC T. | | | 310.16 | | | ALL RECEPTACLES SHALL BE TAMPER RESISTANT. NEC 406.11 | | | RECEPTACLES IN BATHROOMS, KITCHEN AREAS AND OUTDOORS | | | SHALL BE GFCI PROTECTED. NEC 210. 8 | | | | | | | | | ROBERT LECKY | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | |
|