| 2011-07-18 10:32:16 | BUILDING PLAN REVIEW |
| | PERMIT: 11070290 |
| | ADD: 1120 13TH ST |
| | CONT: GENERAL ENGINEERING & DEVELOPMENT |
| | TEL: (561)509-4000 |
| | |
| | 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 2007 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | |
| | 1) COVER SHEET INDICATES A MIXED USE OCCUPANCY AS |
| | BUSINESS/ DAYCARE PLEASE INDICATE WHERE THE BUSINESS |
| | PORTION OF THE MIXED USE OCCUPANCY IS LOCATED. THE |
| | PLANS APPEAR TO BE A DAYCARE OCCUPANCY PER 2007/ 09 |
| | FBC-B 202 DEFINITIONS AND SECTION 436 OF THE FBC-B. |
| | |
| | 2) PLEASE REVIEW THE OCCUPANT LOADS VERSES SQ FT, COVER |
| | SHEET SEE FBC-B TABLE 1004.1.1DAYCARE 20 NET |
| | |
| | 3) OF THE OCCUPANT LOAD FOR THE DAYCARE OCCUPANCY HOW |
| | MANY OF THE OCCUPANTS (CLIENTS) WILL BE 24 MONTHS OLD |
| | OR LESS IN AGE ? 2007/09 FBC-B 436.2. |
| | |
| | 4) PLEASE UPDATE PLANS TO COMPLY WITH : |
| | 4A) 436.2 CLOSET DOORS. EVERY CLOSET DOOR LATCH SHALL |
| | BE SUCH THAT CLIENTS CAN OPEN THE DOOR FROM INSIDE THE |
| | CLOSET. |
| | |
| | 4B) 436.3 BATHROOM DOORS. EVERY BATHROOM DOOR LOCK |
| | SHALL BE DESIGNED TO PERMIT OPENING OF THE LOCKED DOOR |
| | FROM THE OUTSIDE IN AN EMERGENCY. THE OPENING DEVICE |
| | SHALL BE READILY ACCESSIBLE TO THE STAFF. |
| | |
| | 4C) 436.4 DOOR CLOSURE. ANY EXIT DOOR DESIGNED TO BE |
| | NORMALLY CLOSED SHALL BE KEPT CLOSED AND SHALL COMPLY |
| | WITH SECTION 715.3. |
| | |
| | 5) 2007/09 FBC-B 436.1 & 436.2 PLEASE PROVIDE |
| | INFORMATION ON ROOMS OR AREAS OF CONCERN SINCE THEY ARE |
| | NOT INDICATED ON THE PLANS: |
| | 5A) 436.1(3.) ROOMS OR SPACES USED FOR THE STORAGE OF |
| | HAZARDOUS MATERIALS OR FLAMMABLE OR COMBUSTIBLE LIQUIDS |
| | IN QUANTITIES DEEMED HAZARDOUS BY RECOGNIZED STANDARDS. |
| | |
| | 5B) 436.1(4) JANITOR CLOSETS. |
| | |
| | 5C) 436.6.2 ( 1.) LAUNDRIES. |
| | |
| | 5D) 436.2 (4.) ROOMS OR SPACES USED FOR PROCESSING OR |
| | USE OF HAZARDOUS MATERIALS (CLEANING PRODUCTS) OR |
| | FLAMMABLE OR COMBUSTIBLE LIQUIDS IN QUANTITIES DEEMED |
| | HAZARDOUS BY RECOGNIZED STANDARDS. |
| | |
| | 6) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |