Plan Review Notes
Plan Review Notes For Permit 11070251
Permit Number 11070251
Review Stop M
Sequence Number 1
Notes
Date Text
2011-07-13 11:09:462007 FBC W/2009 REVISIONS
  
 MECHANICAL REVISION DENIED
  
 1) SUBMIT TWO SETS OF REVISED ENERGY CALCULATIONS AND
 EQUIPMENT SIZING CALCULATIONS THAT CORRESPOND TO THE
 REVISED 13 SEER EQUIPMENT. THE PREVIOUSLY APPROVED
 EQUIPMENT CONSISTED OF TWO 5 TON AND A 1.5 TON SYSTEMS,
 ALL WERE 14 SEER.
  
 2) ON SHEET M-1, CU-2 IS SPECIFIED AS THE 2 TON UNIT
 AND IN THE EQUIPMENT SCHEDULE ON SHEET M-3, CU-3 IS
 SPECIFIED AS THE 2 TON UNIT. PLEASE CLARIFY.
  
 3) THE CFM IS NOT SPECIFIED AT TWO OF THE SUPPLY
 OUTLETS IN THE SECOND FLOOR SITTING/OFFICE.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved