Plan Review Notes
Plan Review Notes For Permit 11070200
Permit Number 11070200
Review Stop B
Sequence Number 1
Notes
Date Text
2011-07-12 16:01:37RESIDENTIAL (R3) RE-ROOF, BUILDING REVIEW CHECKLIST.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS.
  
  
 1- CONCRETE ROOF TILE NOA 06-0713.05 WAS SUPERSEDED BY
 MIAMI-DADE. VISIT MIAMI-DADE WEBSITE AND DOWNLOAD
 CURRENT NOA. THEN RESUBMIT.
  
 2- SPECIFY HOW IS THE ROOF TILE GOING TO BE INSTALLED
 TO VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC.
 R301 OF 2007 FLORIDA RESIDENTIAL CODE. IF USING SCREWS
 OR NAILS, THEN SPECIFY THE NUMBER OF FASTENERS TO BE
 USED. IF USING ADHESIVE, THEN PROVIDE 2 COPIES OF THE
 PRODUCT APPROVAL AS REQUIRED BY DCA RULE 9N-3.
  
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712