| Plan Review Notes For Permit 11070180 |
| Permit Number |
11070180 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2012-05-09 11:18:41 | 2007 FBC W/2009 REVISIONS | | | | | | DENIED BY BUILDING | | | | | | 1) REVISE THE SCOPE OF WORK ON SHEET A-1 TO INCLUDE | | | FIRE DAMAGE REPAIRS, WINDOW REPLACEMENT, ETC. PLEASE BE | | | SPECIFIC. CITY AMENDMENTS 106.1.1 | | | | | | 2) PROVIDE DETAILS OF ALL STRUCTURAL REPAIRS DUE TO | | | FIRE DAMAGE. CITY AMENDMENTS 106.1.1 AND R301.1 | | | | | | 3) REVISE THE AREA CALCULATIONS ON THE PLAN TO SHOW THE | | | TOTAL HABITABLE AREA AFTER THE ILLEGAL CONVERSION ON | | | THE FIRST FLOOR HAS BEEN CHANGED BACK TO STORAGE. CITY | | | AMENDMENTS 106.1.1 | | | | | | 4) SPECIFY THE REQUIRED DESIGN PRESSURES FOR THE | | | WINDOWS THAT WILL BE REPLACED ON THE PLANS. FBC | | | R301.2.1 | | | | | | 5) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE NEW | | | WINDOWS THAT WILL BE INSTALLED. DCA RULE 9N-3 AND CITY | | | AMENDMENTS 106.1. | | | | | | 6) THE DESIGNER OF RECORD IS REQUIRED TO REVIEW AND | | | APPROVE THE PRODUCT APPROVALS IN WRITING PER CITY | | | AMENDMENTS 106.3.3 | | | | | | 7) PLEASE ADJUST THE VALUE ON THE PERMIT APPLICATION TO | | | $45,000.00 PER OUR TELEPHONE CONVERSATION TO REFLECT | | | THE REVISED SCOPE OF WORK. CITY AMENDMENTS 108.3 | | | | | | 8) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH | | | OF THE REVIEW COMMENTS HAS BEEN ADDRESSED. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|