Plan Review Notes
Plan Review Notes For Permit 11070180
Permit Number 11070180
Review Stop B
Sequence Number 3
Notes
Date Text
2012-05-09 11:18:412007 FBC W/2009 REVISIONS
  
 DENIED BY BUILDING
  
 1) REVISE THE SCOPE OF WORK ON SHEET A-1 TO INCLUDE
 FIRE DAMAGE REPAIRS, WINDOW REPLACEMENT, ETC. PLEASE BE
 SPECIFIC. CITY AMENDMENTS 106.1.1
  
 2) PROVIDE DETAILS OF ALL STRUCTURAL REPAIRS DUE TO
 FIRE DAMAGE. CITY AMENDMENTS 106.1.1 AND R301.1
  
 3) REVISE THE AREA CALCULATIONS ON THE PLAN TO SHOW THE
 TOTAL HABITABLE AREA AFTER THE ILLEGAL CONVERSION ON
 THE FIRST FLOOR HAS BEEN CHANGED BACK TO STORAGE. CITY
 AMENDMENTS 106.1.1
  
 4) SPECIFY THE REQUIRED DESIGN PRESSURES FOR THE
 WINDOWS THAT WILL BE REPLACED ON THE PLANS. FBC
 R301.2.1
  
 5) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE NEW
 WINDOWS THAT WILL BE INSTALLED. DCA RULE 9N-3 AND CITY
 AMENDMENTS 106.1.
  
 6) THE DESIGNER OF RECORD IS REQUIRED TO REVIEW AND
 APPROVE THE PRODUCT APPROVALS IN WRITING PER CITY
 AMENDMENTS 106.3.3
  
 7) PLEASE ADJUST THE VALUE ON THE PERMIT APPLICATION TO
 $45,000.00 PER OUR TELEPHONE CONVERSATION TO REFLECT
 THE REVISED SCOPE OF WORK. CITY AMENDMENTS 108.3
  
 8) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH
 OF THE REVIEW COMMENTS HAS BEEN ADDRESSED.
  