2011-07-12 08:43:28PROVIDE PANEL SCHEDULE AND LOAD CALCULATION. NEC 215.5
 NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11
 REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO
 INCLUDE INTERCONNECTED SMOKE DETECTORS. IF THE
 RESIDENCE HAS GAS APPLIANCES, AN ATTACHED GARAGE OR A
 FIRE PLACE A CARBON MONOXIDE DETECTOR IS REQUIRED
 WITHIN TEN FEET OF EACH ROOM USED FOR SLEEPING. FBC
 R313
 A GFCI PROTECTED RECEPTACLE IS REQUIRED OUTSIDE FRONT
 AND BACK. NEC 210.52
 PROVIDE A 20 AMP BRANCH CIRCUIT FOR THE BATHROOMS. NEC
 210.11 (C)(3)
 PROVIDE TWO OR MORE 20- AMPERE SMALL APPLIANCE BRANCH
 CIRCUITS. NEC 210.52
  