| 2011-07-08 15:53:54 | 2223 PALM BEACH LAKES BOULEVARD, SUITE #102 |
| | PERMIT #11070070 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | THE PLANS INDICATE AN OCCUPANT LOAD OF 727 PERSONS |
| | BASED UPON 15 SQUARE FEET PER PERSON; HOWEVER, HALL #1, |
| | #2, AND #3 ARE BASED UPON 7 SQUARE FEET PER PERSON. |
| | NOTE THE MAIN ENTRANCE SHALL BE ABLE TO HANDLE ONE HALF |
| | THE TOTAL OCCUPANT LOAD. |
| | |
| | NO OCCUPANT LOAD HAS BEEN INDICATED FOR ROOM #112. |
| | |
| | MAXIMUM OCCUPANCY LOADS TO BE POSTED ON PERMANENT SIGNS |
| | INSIDE EACH HALL. |
| | |
| | EACH SMOKE OR FIRE-RATED WALL/PARTITION SHALL BE |
| | PERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING READING |
| | FIRE/SMOKE BARRIER - PROTECT ALL OPENINGS. CHARACTERS |
| | SHALL BE AT LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN |
| | WIDTH. IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15 |
| | FEET ON CENTER. REFERENCE SECTION 8.3.2.4 OF FLORIDA |
| | FIRE PREVENTION CODE ? NFPA 101 |
| | |
| | PENETRATIONS THROUGH A FIRE-RATED WALL ASSEMBLY SHALL |
| | BE PROTECTED BY A FIRESTOP SYSTEM OR DEVICE. REFERENCE |
| | SECTION 8.3.5.1 OF FLORIDA FIRE PREVENTION CODE ? NFPA |
| | 101. PROVIDE FIRESTOPPING DETAILS. |
| | |
| | PROVIDE DOOR SCHEDULE INFORMATION INDICATING DOOR TYPE, |
| | HARDWARE, FIRE RATING, ETC. |
| | |
| | PLANS INDICATE SIX EXITS ARE REQUIRED; ONLY 4 EXTERIOR |
| | DOORS ARE INDICATED AS EXIT DOORS. STORAGE ROOM IS |
| | LABLED WITH EXIT SIGN, BUT EXITING IS NOT PERMITTED |
| | THROUGH THE STORAGE ROOM. |
| | |
| | ADDITIONAL EXIT SIGNS ARE ADVISED FOR CORRIDOR #102. |
| | |
| | PROVIDE TACTILE SIGNAGE AT EXIT DOORS WITH EXIT SIGNS. |
| | |
| | WESLEY JOLIN |
| | WEST PALM BEACH FIRE RESCUE |
| | FIRE & LIFE SAFETY PLAN REVIEW |
| | |