| 2011-07-11 12:01:11 | BUILDING PLAN REVIEW |
| | PERMIT: 11070070 |
| | ADD: 2223 PALM BEACH LAKES # 102 |
| | CONT: LTA INC. |
| | TEL: (561)635-8478 |
| | |
| | 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 2007 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) DESCREPENCIES IN PLANS: |
| | |
| | 1A) SHEET A-4 INDICATES IN HALL #4 THE FRONT EXIT DOOR |
| | AS A SINGLE SWING DOOR WHERE AS A-3 INDICATES A PAIR OF |
| | DOUBLE DOORS. |
| | |
| | 1B) SHEET A-2 INDICATES AT THE REAR OF THE BUILDING A |
| | OVERHEAD DOOR ON A-3 & A-4 THIS DOOR IS PARTIALLY FILED |
| | IN AND AN OPENING IS LEFT? PLANS DO NOT PORVIDE |
| | DETAILS FOR HOW IS OPENING WILL BE BLOCKED IN AND WHAT |
| | WILL OCCUR IN THE OPENING INDICATED. |
| | |
| | 2) PLEASE PROVIDE A LIFE SAFETY PLAN INDICATING WHERE |
| | THE OCCUPANTS WILL BE EXITING THROUGH WHICH EXITS. |
| | COMPLY WITH 1025.2 ASSEMBLY MAIN EXIT. EVERY ASSEMBLY |
| | OCCUPANCY SHALL BE PROVIDED WITH A MAIN ENTRANCE/EXIT. |
| | THE MINIMUM AGGREGATE WIDTH OF THE MAIN ENTRANCE FOR |
| | GROUP A OCCUPANCIES SHALL BE SUFFICIENT TO ACCOMMODATE |
| | 50 PERCENT OF THE OCCUPANT LOAD AND SHALL BE AT THE |
| | LEVEL OF EXIT DISCHARGE OR SHALL CONNECT TO A STAIRWAY |
| | OR RAMP LEADING TO A STREET. PLEASE NOTE THAT 114 |
| | OCCUPANTS ARRE NOT INDICATED IN ROOM #112. |
| | |
| | 3) IF VARIOUS EXTERIOR OPENINGS ARE GOING TO BE |
| | MODIFIED THEN THE WIND DESIGN CRITERIA WILL BE |
| | REQUIRED: |
| | |
| | 1609.6.2 WIND DESIGN PROCEDURES |
| | 3.1) THE BASIC WIND SPEED, V, SHALL BE DETERMINED IN |
| | ACCORDANCE WITH SECTION 1609.3. THE WIND SHALL BE |
| | ASSUMED TO COME FROM ANY HORIZONTAL DIRECTION. |
| | |
| | 3.2) AN IMPORTANCE FACTOR, IW, SHALL BE DETERMINED IN |
| | ACCORDANCE WITH SECTION1609.5. |
| | |
| | 3.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN |
| | ACCORDANCE WITH 1609.4. |
| | |
| | 3.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, * |
| | SHALL BE DETERMINED FROM TABLE 1609.6.2.1(4) |
| | |
| | 3.5) PRESSURES BOTH POSITIVE & NEGATIVE. |
| | |
| | 4) FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING, |
| | PROVIDE 2 COPIES, |
| | 3 IF THRESHOLD OR RESIDENT INSPECTOR OF PRODUCT TESTING |
| | REPORTS, MISSING REPORTS ARE AS FOLLOWS: |
| | EXTERIOR GLADED DOUBLE DOORS |
| | EXTERIOR STEEL DOORS |
| | |
| | 5) 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE |
| | REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND |
| | APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO |
| | SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | 6) HALL# 4 WITH THE OCCUPANT LOAD OF 300 INDICATES TWO |
| | NEW DOORWAYS BEING CUT INTO WALL TYPE "A" A TENANT |
| | SEPERATION WALL, IS THIS NEW TENANT SPACE OR A SEPERATE |
| | TENANT OR ARE ALL FOUR HALLS UNDER THE SAME TENANTCY? |
| | 1014.2.1 MULTIPLE TENANTS. WHERE MORE THAN ONE TENANT |
| | OCCUPIES ANY ONE FLOOR OF A BUILDING OR STRUCTURE, EACH |
| | TENANT SPACE, DWELLING UNIT AND SLEEPING UNIT SHALL BE |
| | PROVIDED WITH ACCESS TO THE REQUIRED EXITS WITHOUT |
| | PASSING THROUGH ADJACENT TENANT SPACES, DWELLING UNITS |
| | AND SLEEPING UNITS. |
| | |