| 2011-07-11 08:31:37 | BUILDING PLAN REVIEW |
| | PERMIT: 11070054 |
| | ADD: 771 VILLAGE BLVD SUITE 212-213 |
| | CONT: TO BE DETERMINED |
| | TEL: (954)583-9990 |
| | |
| | 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 2007 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) CONTRACTOR TO SIGN ONTO PERMIT APPLICATION BEFORE |
| | ISSANCE, VERIFY LICENSURE AND INSURANCE. |
| | |
| | 2) SHEET A1 NOTE #8 INDICATES THE WATER HEATER TO BE |
| | INSTALLED OVER THE RESTROOM CEILING, PLEASE SEE SHEET |
| | A2.1 DETAIL # 7 INDICATES TTHE WATER HEATER LOCATION TO |
| | BE OVER THE JANITORS CLOSET, EVEN THE PLUMBING SHEET |
| | P-3 THE TWO ISOMETRICS INDICATE THE WATER HEATER IN TWO |
| | LOCATIONS. |
| | |
| | 3) PLEASE ALSO PROVIDE ADDITIONAL DETAILS FOR POINT |
| | LOADING OF THE BAR JOIST: |
| | 3A) IF THE LOCATION OF TTHE WATER HEATER IS OVER THE |
| | JANITORS CLOSET THE BAR JOIST BOTTOM CHORD USALLY DOES |
| | NOT CONTINUE TO THE BEARING WALL AND BRIDGING IS USALLY |
| | WELDED ONTO THE BOTTOM CHORD, IF THIS CONDITION EXIST |
| | HOW WILL THE HEATER BE HUNG FROM BAR JOIST. |
| | |
| | 3B) IF THE LOCATION OF THE WATER HEATER IS LOCATED OVER |
| | THE RESTROOM PLEASE LOCATE ON PLANS? |
| | |
| | 4) SHEET A2.1 NOTE #1 INDICATES THE STOREFRONT TO BE |
| | REMOVED AND NEW SYSTEM TO INSTALLED: |
| | |
| | 4A) MISSING WIND DESIGN, 1609.6.2 WIND DESIGN |
| | PROCEDURES |
| | 4A)1) THE BASIC WIND SPEED, V, SHALL BE DETERMINED IN |
| | ACCORDANCE WITH SECTION 1609.3. THE WIND SHALL BE |
| | ASSUMED TO COME FROM ANY HORIZONTAL DIRECTION. |
| | |
| | 4A) 2) AN IMPORTANCE FACTOR, IW, SHALL BE DETERMINED IN |
| | ACCORDANCE WITH SECTION1609.5. |
| | |
| | 4A) 3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN |
| | ACCORDANCE WITH 1609.4. |
| | |
| | 4A) 4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, * |
| | SHALL BE DETERMINED FROM TABLE 1609.6.2.1(4) |
| | |
| | 4A) 5) PRESSURES +/-. |
| | |
| | 5) FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING, |
| | PROVIDE 2 COPIES OF PRODUCT TESTING REPORTS, MISSING |
| | REPORTS ARE AS FOLLOWS: |
| | 1) STOREFRONT DOOR |
| | |
| | 2) STOREFRONT GLAZING |
| | |
| | 3) STORM SHUTTERS IF LARGE MISSILE IMPACT RESISTANT |
| | TESTED GLAZING SYSTEMS IS NOT INSTALLED. |
| | |
| | 6) 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE |
| | REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND |
| | APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO |
| | SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | 7) SHEET A2.1 NOTE NOTE # 2 INDICATEES PEIR TO BE |
| | REPLACED, PLEASE PROVIDE DETAILS TO WHAT IS THE |
| | STRUCTURAL BASE OF THIS PIER AND WHAT WILL BE ADDED TO |
| | THIS PIER FOR THE WINDOW FRAME TO ATTACH TO FOR |
| | ANCHORING. 2007/ 09 FBC-B 1609 WIND LOADING AND PART OF |
| | THE MWFRS. |
| | |
| | JAMES A. WITMER C.B.O. |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: (561)805-6715 |
| | FAX:(561)805-6731 |
| | E-MAIL: [email protected] |
| | |