| Plan Review Notes For Permit 11070051 |
| Permit Number |
11070051 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-07-15 09:59:12 | 7643-7645 SOUTH DIXIE HIGHWAY | | | PERMIT #11070051 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | ALL DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS | | | OF NFPA 241. | | | | | | FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING | | | DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A | | | FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN | | | 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE | | | PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST | | | BE APPROVED AND SUBMITTED IN WRITING TO THE OFFICE OF | | | THE FIRE MARSHAL. | | | | | | PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY | | | RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING | | | NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM | | | WWW.KNOXBOX.COM. | | | | | | PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH | | | EXIT SIGNS. | | | | | | EMERGENCY PLAN TO BE DEVELOPED AND POSTED IN BUILDING | | | PRIOR TO OCCUPANCY. | | | | | | EMERGENCY EGRESS DRILLS SHALL BE CONDUCTED MONTHLY. ALL | | | DRILLS SHALL BE SOUNDED ON THE FIRE ALARM SYSTEM. | | | | | | ARTWORK AND TEACHING MATERIALS ATTACHED TO THE WALLS | | | SHALL NOT EXCEED 50 PERCENT OF THE INDIVIDUAL WALL | | | AREA. | | | | | | WESLEY JOLIN | | | WEST PALM BEACH FIRE RESCUE | | | FIRE & LIFE SAFETY PLAN REVIEW | | | |
|