| Plan Review Notes For Permit 11070051 |
| Permit Number |
11070051 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-07-14 11:16:14 | BUILDING PROVISO: | | | 1) 2007/09 FBC-B TABLE 1017.1 FOOTNOTE ?C? | | | C. IN BUILDINGS PROTECTED THROUGHOUT BY AN APPROVED, | | | SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE | | | WITH SECTION 903, CORRIDOR WALLS SHALL NOT | | | BE REQUIRED TO BE RATED, PROVIDED THAT SUCH WALLS FORM | | | SMOKE PARTITIONS IN ACCORDANCE WITH THE FLORIDA FIRE | | | PREVENTION CODE. | | | | | | 710.4 CONTINUITY. SMOKE PARTITIONS SHALL EXTEND FROM | | | THE TOP OF THE FOUNDATION OR FLOOR BELOW TO THE | | | UNDERSIDE OF THE FLOOR OR ROOF SHEATHING, DECK OR SLAB | | | ABOVE OR TO THE UNDERSIDE OF THE CEILING ABOVE WHERE | | | THE CEILING MEMBRANE IS CONSTRUCTED TO LIMIT THE | | | TRANSFER OF SMOKE. | | | | | | 712.6 FIRE WALLS, FIRE BARRIERS, FIRE PARTITIONS, SMOKE | | | BARRIERS AND SMOKE PARTITIONS OR ANY OTHER WALL | | | REQUIRED TO HAVE PROTECTED OPENINGS SHALL BE | | | EFFECTIVELY AND PERMANENTLY IDENTIFIED WITH SIGNS OR | | | STENCILING IN A MANNER ACCEPTABLE TO THE AUTHORITY | | | HAVING JURISDICTION. SUCH IDENTIFICATION SHALL BE ABOVE | | | ANY DECORATIVE CEILING AND IN CONCEALED SPACES. | | | SUGGESTED WORDING FOR FIRE AND SMOKE BARRIERS: "FIRE | | | AND SMOKE BARRIER - PROTECT ALL OPENINGS." | | | |
|