| Plan Review Notes For Permit 11070027 |
| Permit Number |
11070027 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-07-13 14:09:44 | 2007 FBC W/2009 REVISIONS | | | | | | DENIED BY PLUMBING | | | | | | 1) THE BATHROOM FIXTURES ARE NOT PROPERLY VENTED. IN | | | HORIZONTAL WET-VENT SYSTEMS, NOT MORE THAN ONE | | | WET-VENTED FIXTURE DRAIN SHALL DISCHARGE UPSTREAM OF | | | THE DRY-VENTED FIXTURE DRAIN CONNECTION PER FBCR | | | P3108.2. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|