| Plan Review Notes For Permit 11060799 |
| Permit Number |
11060799 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-07-05 15:42:04 | 1/0 CONDUCTORS ARE REQUIRED FOR SIX SERVICE FEEDERS TO | | | TWO 150 AMP PANELS. NEC T. 310.16, 310.15 (B)(6) | | | THE LOAD CALCULATION IS MISSING THE GENERAL LIGHTING | | | LOAD AS PART OF THE CALCULATION. NEC 220.82 | | | PROVIDE AN INTERSYSTEM BONDING STRIP AT THE SERVICE | | | GROUND. NEC 250.94 | | | | | | ROBERT LECKY | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | |
|