| Notes |
| Date |
Text |
| 2011-07-18 15:36:01 | ELECTRICAL PLAN REQUIRED. | | | | | | INDICATE THE SIZE, RATING, VOLTAGE, LOCATION OF THE | | | EXISTING SERVICE, MAIN DISCONNECTS AND PANELBOARD. | | | PROVIDE PANEL SCHEDULES AND LOAD CALCULATION. PROVIDE | | | AN ELECTRICAL RISER DIAGRAM. INCLUDE NEW AND EXISTING | | | LOADS. NEC 215.5 | | | PROVIDE DEDICATED 20 AMP BRANCH CIRCUITS AS REQUIRED | | | FOR BATH ROOM AND KITCHEN AREAS. NEC 210.11 | | | ADD RECEPTACLES SO THAT NO WALL SPACE IS MORE THAN 6 | | | FEET FROM A RECEPTACLE AND ALL WALL SPACES MORE THAN 2 | | | FEET IN WIDTH HAVE A RECEPTACLE. NEC 210.52 | | | RECEPTACLES ARE REQUIRED IN HALLWAYS. NEC 210.52 (H) | | | GFCI PROTECTED RECEPTACLES ARE REQUIRED ON THE | | | BALCONIES. NEC 210.52(E) | | | ALL GENERAL PURPOSE OUTLETS INCLUDING THOSE IN THE | | | BEDROOMS AND SMOKE ALARMS MUST BE AFCI PROTECTED. NEC | | | 210.12(B) | | | NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11 | | | AT LEAST ONE WALL SWITCH-CONTROLLED LIGHTING OUTLET IS | | | REQUIRED IN EVERY HABITABLE ROOM. NEC 210.70 (A)(1). | | | REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO | | | INCLUDE INTERCONNECTED SMOKE DETECTORS. IF THE | | | RESIDENCE HAS GAS APPLIANCES, AN ATTACHED GARAGE OR A | | | FIRE PLACE A CARBON MONOXIDE DETECTOR IS REQUIRED | | | WITHIN TEN FEET OF EACH ROOM USED FOR SLEEPING. FBC | | | R313 | | | | | | ROBERT LECKY | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | | | | |
|