Plan Review Notes
Plan Review Notes For Permit 11060793
Permit Number 11060793
Review Stop E
Sequence Number 1
Notes
Date Text
2011-07-18 15:36:01ELECTRICAL PLAN REQUIRED.
  
 INDICATE THE SIZE, RATING, VOLTAGE, LOCATION OF THE
 EXISTING SERVICE, MAIN DISCONNECTS AND PANELBOARD.
 PROVIDE PANEL SCHEDULES AND LOAD CALCULATION. PROVIDE
 AN ELECTRICAL RISER DIAGRAM. INCLUDE NEW AND EXISTING
 LOADS. NEC 215.5
 PROVIDE DEDICATED 20 AMP BRANCH CIRCUITS AS REQUIRED
 FOR BATH ROOM AND KITCHEN AREAS. NEC 210.11
 ADD RECEPTACLES SO THAT NO WALL SPACE IS MORE THAN 6
 FEET FROM A RECEPTACLE AND ALL WALL SPACES MORE THAN 2
 FEET IN WIDTH HAVE A RECEPTACLE. NEC 210.52
 RECEPTACLES ARE REQUIRED IN HALLWAYS. NEC 210.52 (H)
 GFCI PROTECTED RECEPTACLES ARE REQUIRED ON THE
 BALCONIES. NEC 210.52(E)
 ALL GENERAL PURPOSE OUTLETS INCLUDING THOSE IN THE
 BEDROOMS AND SMOKE ALARMS MUST BE AFCI PROTECTED. NEC
 210.12(B)
 NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11
 AT LEAST ONE WALL SWITCH-CONTROLLED LIGHTING OUTLET IS
 REQUIRED IN EVERY HABITABLE ROOM. NEC 210.70 (A)(1).
 REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO
 INCLUDE INTERCONNECTED SMOKE DETECTORS. IF THE
 RESIDENCE HAS GAS APPLIANCES, AN ATTACHED GARAGE OR A
 FIRE PLACE A CARBON MONOXIDE DETECTOR IS REQUIRED
 WITHIN TEN FEET OF EACH ROOM USED FOR SLEEPING. FBC
 R313
  
 ROBERT LECKY
 COMMERCIAL COMBINATION PLANS EXAMINER
 [email protected]
 561-805-6718
  
  