2011-07-13 08:36:59BUILDING PLAN REVIEW
 PERMIT: 11060793
 ADD: 1401 VILLAGE BLVD # 1715
 CONT: AMERICAN STANDARD CONSTRUCTION
 TEL: (954)655-5111
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) CONTRACTOR TO TAKE RESPONSIBILITY FOR PLANS, PRINT
 NAME, SIGN NAME AND PRINT LICENSE NUMBER ON PLANS.
  
 2) TO BRING IN VERIFICATION OF NEW OWNERS, PALM BEACH
 COUNTY INDICATES A DIFFERNT OWNER TO THIS UNIT.
  
 3) CONTRACTOR TO INDICATE COMPLIANCE WITH:
 3A) DRYWALL THICKNESS FOR TENANT SEPERATION WALLS AND
 CEILING.
 708.1 GENERAL. THE FOLLOWING WALL ASSEMBLIES SHALL
 COMPLY WITH THIS SECTION: (7). WALL SEPARATING
 INDIVIDUAL TENANT SPACES.
 708.3 FIRE-RESISTANCE RATING. FIRE PARTITIONS SHALL
 HAVE A FIRE-RESISTANCE RATING OF NOT LESS THAN 1 HOUR.
 709.3 FIRE-RESISTANCE RATING. (FLOOR/CEILING
 ASSEMBLIES) A 1-HOUR FIRE-RESISTANCE RATING IS REQUIRED
 FOR SMOKE BARRIERS.
  
 4) 1207.2 AIR-BORNE SOUND. WALLS, PARTITIONS AND
 FLOOR/CEILING ASSEMBLIES SEPARATING DWELLING UNITS FROM
 EACH OTHER OR FROM PUBLIC OR SERVICE AREAS SHALL HAVE A
 SOUND TRANSMISSION CLASS (STC) OF NOT LESS THAN 50 (45
 IF FIELD TESTED) FOR AIR-BORNE NOISE WHEN TESTED IN
 ACCORDANCE WITH ASTM E 90. PENETRATIONS OR OPENINGS IN
 CONSTRUCTION ASSEMBLIES FOR PIPING; ELECTRICAL DEVICES;
 RECESSED CABINETS; BATHTUBS; SOFFITS; OR HEATING,
 VENTILATING OR EXHAUST DUCTS SHALL BE SEALED, LINED,
 INSULATED OR OTHERWISE TREATED TO MAINTAIN THE REQUIRED
 RATINGS. THIS REQUIREMENT SHALL NOT APPLY TO DWELLING
 UNIT ENTRANCE DOORS; HOWEVER, SUCH DOORS SHALL BE TIGHT
 FITTING TO THE FRAME AND SILL.
  
 5) 1207.3 STRUCTURE-BORNE SOUND. FLOOR/CEILING
 ASSEMBLIES BETWEEN DWELLING UNITS OR BETWEEN A DWELLING
 UNIT AND A PUBLIC OR SERVICE AREA WITHIN THE STRUCTURE
 SHALL HAVE AN IMPACT INSULATION CLASS (IIC) RATING OF
 NOT LESS THAN 50 (45 IF FIELD TESTED) WHEN TESTED IN
 ACCORDANCE WITH ASTM E 492.
  
 JAMES A. WITMER
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX561-805-6676