| Plan Review Notes For Permit 11060778 |
| Permit Number |
11060778 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-07-18 13:34:29 | **PROVISO** | | | DESIGN CHANGES ON THIS REVISION HAVE ELIMINATED DUCTED | | | RETURNS AND CREATED A COMMON RETURN AIR PLENUM FOR ALL | | | AIR HANDLING EQUIPMENT ABOVE THE CEILING. DUCT SMOKE | | | DETECTORS ARE REQUIRED ON THE SUPPLY AND RETURN SIDE OF | | | EACH PIECE OF AIR HANDLING EQUIPMENT PER FBC-M 606.2.2. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|