Plan Review Notes
Plan Review Notes For Permit 11060769
Permit Number 11060769
Review Stop B
Sequence Number 1
Notes
Date Text
2011-07-06 09:43:19BUILDING PLAN REVIEW
 PERMIT: 11060769
 ADD: 2277 EGRET COVE DRIVE
 CONT: SUNSHINE ALUMINUM
 TEL: (561)842-3643
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) B D Q ENGINEERING SHEET INDICATES THIS JOBSITE
 LOCATION IS LOCATED WITH-IN A "B" EXPOSURE, THIS JOB IS
 LOCATED NEXT TO A LAKE, PLEASE REVIEW SECTION:
 2007/09 FBC-B 1609.4.3 EXPOSURE CATEGORIES. EXPOSURE C.
 OPEN TERRAIN WITH SCATTERED OBSTRUCTIONS, INCLUDING
 SURFACE UNDULATIONS OR OTHER IRREGULARITIES, HAVING
 HEIGHTS GENERALLY LESS THAN 30 FEET (9144 MM) EXTENDING
 MORE THAN 1,500 FEET (457.2 M) FROM THE BUILDING SITE
 IN ANY QUADRANT. THIS EXPOSURE SHALL ALSO APPLY TO ANY
 BUILDING LOCATED WITHIN EXPOSURE B-TYPE TERRAIN WHERE
 THE BUILDING IS WITHIN 100 FEET HORIZONTALLY IN ANY
 DIRECTION OF OPEN AREAS OF EXPOSURE C-TYPE TERRAIN THAT
 EXTENDS MORE THAN 600 FEET (182.9 M) AND WIDTH GREATER
 THAN 150 FT. IN THE UPWIND DIRECTION.
  
 2) SUNSHINE ALUMINUM SHEET INDICATES THERE TO BE NEW
 FOUNDATIONS, THE BDQ SHEET HAS A NOTE WHEN THE
 INSTALATION OF BRICK PAVERS ARE TO INSTALLED A FOUR
 INCH THICK CONCRETE, THE PLANS DO NOT INDICATE THIS TO
 BE A FOOTER, THE MINIMUM PSI OF THE CONCRETE NOR IF THE
 CONCRETE IS TO HAVE ANY REINFORCING IN THE POUR. THE
 SECOND ISSUE IS HOW THICK OF A PAVER BRICK IS TO BE
 INSTALLED WITH THIS TYPE OF INSTALATION. IS THE PAVER
 BRICK TO BE GROUTED TO THE FOOTER OR WILL THERE BE A
 LIMESTONE SREENING BED BETWEEN THE FOOTER AND PAVER
 BRICK, IF SO HOW MUCH OF A SCREENING BED IS TO BE
 INSTALLED? WHAT WILL THE MINIMUM EMBEDMENT OF THE SIX
 INCH TAPCON INTO THE CONCRETE FOUNDATION AND WHAT WOULD
 THE MINIMUM DIAMETER OF THE TAPCON ANCHOR BE?
 ADDITIONAL INFORMATION REQUIRED. 106.1.2.
  
 3) UPDATE WALL COLUMN SCHEDULE TO THE "C" EXPOSURE AND
 ASSOCIATED PRESSURES.
  
 JAMES A. WITMER C.B.O.
 COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: (561)805-6715
 FAX:(561)805-6731
 E-MAIL: [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved