Plan Review Notes
Plan Review Notes For Permit 11060763
Permit Number 11060763
Review Stop M
Sequence Number 4
Notes
Date Text
2011-09-06 12:16:30OK TO ISSUE W/PROVISO PER HM
 PLAN SUBMITTED UNDER 11080552 (FILED UNDER MASTER
 11060763, INCLUDES ELECTRICAL FOR LOFT)
  
  
 ****PROVISO****
 ****REVISION REQUIRED****
 ****ISSUED AT CONTRACTOR'S RISK****
  
 SHOW COMPLIANCE WITH FBC MECHANICAL 403
  
 LETTER SUBMITTED APPEARS TO PROVIDE ASHRAE 62
 CALCULATIONS. FOR RETAIL SPACE, OUTDOOR AIR IS TO BE
 DETERMINED BASED ON OCCUPANCY LEVEL AND FLOOR AREA
 (ONLY FLOOR AREA WAS USED).
  
 LETTER SUBMITTED IS NOT SIGNED AND SEALED, FS471.
 PLEASE INCORPORATE OUTDOOR AIR CALCULATIONS INTO THE
 PLAN.
  
 PLAN IS TO SHOW HOW OUTDOOR AIR WILL BE SUPPLIED (WHICH
 UNITS, CFM PER UNIT).
  
 INCORPORATE WIND DESIGN CRITERIA INTO THE PLAN.
  
  
  
  