| Plan Review Notes For Permit 11060763 |
| Permit Number |
11060763 |
|
| Review Stop |
M |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2011-09-06 12:16:30 | OK TO ISSUE W/PROVISO PER HM | | | PLAN SUBMITTED UNDER 11080552 (FILED UNDER MASTER | | | 11060763, INCLUDES ELECTRICAL FOR LOFT) | | | | | | | | | ****PROVISO**** | | | ****REVISION REQUIRED**** | | | ****ISSUED AT CONTRACTOR'S RISK**** | | | | | | SHOW COMPLIANCE WITH FBC MECHANICAL 403 | | | | | | LETTER SUBMITTED APPEARS TO PROVIDE ASHRAE 62 | | | CALCULATIONS. FOR RETAIL SPACE, OUTDOOR AIR IS TO BE | | | DETERMINED BASED ON OCCUPANCY LEVEL AND FLOOR AREA | | | (ONLY FLOOR AREA WAS USED). | | | | | | LETTER SUBMITTED IS NOT SIGNED AND SEALED, FS471. | | | PLEASE INCORPORATE OUTDOOR AIR CALCULATIONS INTO THE | | | PLAN. | | | | | | PLAN IS TO SHOW HOW OUTDOOR AIR WILL BE SUPPLIED (WHICH | | | UNITS, CFM PER UNIT). | | | | | | INCORPORATE WIND DESIGN CRITERIA INTO THE PLAN. | | | | | | | | | | | | |
|