| 2011-08-08 13:06:45 | ****CORRECTIONS**** |
| | 11060763 |
| | |
| | 1-2. ADDRESSED. |
| | |
| | 3. SHOW COMPLIANCE WITH VENTILATION RATES REQUIRED BY |
| | FBC MECHANICAL 403, FBC EXISTING BUILDING 909. NOT |
| | ENOUGH INFORMATION PROVIDED REGARDING PREVIOUS USE AND |
| | PROPOSED USE TO DETERMINE REQUIREMENTS OR COMPLIANCE. |
| | |
| | 2ND REVIEW, COMMENT NOT ADDRESSED. A NOTE ON THE PLAN |
| | WAS ADDED WHICH STATES THAT "OUTDOOR FRESHAIR WAS |
| | CALCULATED AT THE FOLLOWING UNDER TABLE 6-1 MINIMUM |
| | VENTILATION RATES IN BREATHING ZONES." SHOW COMPLIANCE |
| | BY PROVIDING CALCULATIONS, SEE FBC MECHANICAL 403. |
| | |
| | 4. SEE FIRE COMMENTS REGARDING PERMITTING OF THE LOFT. |
| | PLEASE ADDRESS AS THE PLAN SUBMITTED PROPOSES TO USE |
| | THIS AREA FOR MECHANICAL EQUIPMENT. FBC MECHANICAL |
| | 302.1. |
| | |
| | 2ND REVIEW, COMMENT NOT ADDRESSED. RESPONSE LETTER |
| | STATES THAT THIS IS CLOSED OFF. THE LOFT, WHICH IS |
| | PROPOSED TO BE USED FOR MECHANICAL EQUIPMENT AND |
| | MAINTENANCE, HAS NOT BEEN PERMITTED OR INSPECTED. THIS |
| | MAY BE INCLUDED IN SCOPE OF WORK UNDER THIS PERMIT; |
| | INCLUDE ALL STRUCTURAL INFORMATION AND REVISE VALUE. |
| | |
| | 5. PROVIDE MANUFACTURER SPECIFICATIONS WHICH SHOW THAT |
| | INTERIOR INSTALLATION OF MECHANICAL EQUIPMENT IS |
| | PERMITTED, FBC MECHANICAL 304.1. IF INTERIOR |
| | INSTALLATION OF EQUIPMENT IS ALLOWED PER MANUFACTURER |
| | SPECIFICATIONS, PROVIDE INFORMATION REGARDING HOW THE |
| | FAN DISCHARGE (EXHAUST) AIR WILL BE ADDRESSED, FBC |
| | MECHANICAL CHAPTER 5. |
| | |
| | 2ND REVIEW, THIS WAS ADDRESSED BY MOVING THE ACU TO THE |
| | ROOF. A NOTE WAS ADDED WHICH STATES THAT THE ROOFTOP |
| | UNITS WILL BE ANCHORED TO THE ROOF JOISTS. PROVIDE A |
| | DETAIL FOR A CURB OR PROVIDE THE ROOF STAND PRODUCT |
| | APPROVAL. INCLUDE A STATEMENT THAT ATTACHMENT DETAIL |
| | COMPLIES WITH WIND DESIGN CRITERIA OF 140MPH. |
| | |
| | 6-7. ADDRESSED. |
| | |
| | 8. HORN AND STROBE NOTIFICATION REQUIRED, FBC M 606.4. |
| | |
| | 2ND REVIEW, RESPONSE LETTER STATES THAT A STROBE IS NOT |
| | REQUIRED. PLEASE SEE FBC M 606.4.1, SUPERVISION AND |
| | REVISE PLAN TO SHOW COMPLIANCE. |
| | |
| | 9-11. ADDRESSED. |
| | |
| | NEW COMMENT: |
| | |
| | 12. PLEASE EXPLAIN, WHO IS "RICHARD A. JEMISON"? IT IS |
| | NOT CLEAR WHY THE PLANS STATE THAT THIS INDIVIDUAL |
| | DESIGNED THE JOB BUT FREDERICK D SHAFFER SIGNED AND |
| | SEALED THE PLAN. PLEASE SHOW HOW MR. JEMISON IS |
| | LICENSED TO DESIGN THIS SCOPE OF WORK UNDER FS 471, |
| | 481, 489 OR OTHER FLORIDA STATUTE. THIS APPEARS TO BE |
| | SPECIFICALLY PROHIBITED. |
| | |
| | HAROLD MOSER, MECHANICAL PLANS EXAMINER |