| 2011-07-13 09:01:03 | ****CORRECTIONS**** |
| | 11060763 |
| | |
| | 1. PROVIDE HEAT LOAD CALCULATIONS, FBC MECHANICAL 312. |
| | |
| | 2. PROVIDE AN EQUIPMENT SCHEDULE, FBC 106. |
| | |
| | 3. SHOW COMPLIANCE WITH VENTILATION RATES REQUIRED BY |
| | FBC MECHANICAL 403, FBC EXISTING BUILDING 909. NOT |
| | ENOUGH INFORMATION PROVIDED REGARDING PREVIOUS USE AND |
| | PROPOSED USE TO DETERMINE REQUIREMENTS OR COMPLIANCE. |
| | |
| | 4. SEE FIRE COMMENTS REGARDING PERMITTING OF THE LOFT. |
| | PLEASE ADDRESS AS THE PLAN SUBMITTED PROPOSES TO USE |
| | THIS AREA FOR MECHANICAL EQUIPMENT. FBC MECHANICAL |
| | 302.1. |
| | |
| | 5. PROVIDE MANUFACTURER SPECIFICATIONS WHICH SHOW THAT |
| | INTERIOR INSTALLATION OF MECHANICAL EQUIPMENT IS |
| | PERMITTED, FBC MECHANICAL 304.1. IF INTERIOR |
| | INSTALLATION OF EQUIPMENT IS ALLOWED PER MANUFACTURER |
| | SPECIFICATIONS, PROVIDE INFORMATION REGARDING HOW THE |
| | FAN DISCHARGE (EXHAUST) AIR WILL BE ADDRESSED, FBC |
| | MECHANICAL CHAPTER 5. |
| | |
| | 6. FAN SHUTDOWNS REQUIRED, FBC M 606.4. |
| | |
| | 7. DUCT SMOKE DETECTORS REQUIRED, FBC M 606.2.1. |
| | |
| | 8. HORN AND STROBE NOTIFICATION REQUIRED, FBC M 606.4. |
| | |
| | 9. CONDITIONED SPACE (SEE DEFINITIONS) TO COMPLY WITH |
| | REQUIREMENTS OF FBC 13 101.3, FBC 13 101.4. NOT ENOUGH |
| | INFORMATION PROVIDED TO DETERMINE COMPLIANCE OR |
| | REQUIREMENTS. |
| | |
| | 9. THE FACT THAT THE SYSTEM IS FOR DEHUMIDIFICATION |
| | ONLY IS NOTED. IF COMPLIANCE IS NOT SHOWN FOR A SPACE |
| | COOLING SYSTEM, THE DESCRIPTION FOR THE PROJECT WILL BE |
| | MODIFIED TO INCLUDE THIS INFORMATION AND WILL BE |
| | AVAILABLE AS PUBLIC RECORD. |
| | |
| | 10. SHOW COMPLIANCE WITH REQUIREMENTS OF FBC 13 407, |
| | HUMIDITY CONTROL. |
| | |
| | 11. NO THERMOSTATS SHOWN. SEE FBC 13 1-01.5.7, FBC 13 |
| | 407AB, IT IS NOT CLEAR HOW HEAT WILL BE REGULATED. |
| | |
| | 12. NOT ENOUGH INFORMATION PROVIDED TO DETERMINE CODE |
| | COMPLIANCE. |
| | |
| | HAROLD MOSER, MECHANICAL PLANS EXAMINER |