2011-07-06 16:17:02417 BUNKER ROAD
 PERMIT #11060763
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THIS RENOVATION APPEARS TO BE A CHANGE OF OCCUPANCY
 FROM INDUSTRIAL/FACTORY TO STORAGE AND MERCANTILE.
 DESIGN SHALL CONFORM TO THE FLORIDA FIRE PREVENTION
 CODE 2007 EDITION: NFPA 1 AND NFPA 101 - 2006 EDITION
 WITH FLORIDA AMENDMENTS.
  
 STRUCTURES WITH LIGHT FRAME FLOOR/ROOF TRUSS
 CONSTRUCTION SHALL BE IDENTIFIED WITH A SIGN AFFIXED TO
 THE BUILDING. THE SIGN SHALL FEATURE A MALTESE CROSS
 8-INCHES WIDE AND 8-INCHES TALL AND BE OF A BRIGHT RED
 REFLECTIVE COLOR AND BEAR THE APPROPRIATE LETTERS "RF"
 DESIGNATION PER FLORIDA STATUTE 633.027 AND FLORIDA
 ADMINISTRATIVE CODE 69A-60.0081.
  
 DOORS IN THE MEANS OF EGRESS SHALL BE SIDE SWINGING.
  
 PROVIDE A DOOR SCHEDULE. INDICATE DOOR HARDWARE.
  
 DOOR IS REQUIRED TO SWING IN THE DIRECTION OF EGRESS
 TRAVEL FOR AN OCCUPANT LOAD OF 50 OR GREATER PERSONS
 PER SECTION 7.2.1.4.2 OF THE FLORIDA FIRE PREVENTION
 CODE: NFPA 101 - LIFE SAFETY CODE.
  
 EXTINGUISHERS SHALL HAVE A MINIMUM RATING OF 2A:10BC
 AND SHALL BE TAGGED BY A LICENSED FIRE EXTINGUISHER
 COMPANY.
  
 THE RELEASING MECHANISM ON ALL DOORS SHALL OPEN THE
 DOOR WITH NOT MORE THAN ONE RELEASING OPERATION. THE
 RELEASING MECHANISM SHALL HAVE AN OBVIOUS METHOD OF
 OPERATION THAT IS READILY OPERATED UNDER ALL LIGHTING
 CONDITIONS. THE RELEASING DEVICE SHOULD BE CAPABLE OF
 BEING OPERATED WITH ONE HAND AND SHOULD NOT REQUIRE
 TIGHT GRASPING, TIGHT PINCHING OR TWISTING OF THE WRIST
 TO OPERATE PER SECTION 7.2.1.5.9 OF NFPA 101 FLORIDA
 EDITION 2007.
  
 THE EXISTING MEZZANINE AND STAIR APPEAR TO HAVE BEEN
 CONSTRUCTED WITHOUT A PERMIT AS STAIRS AND MEZZANINE
 GUARDS DO NOT COMPLY WITH THE FLORIDA FIRE PREVENTION
 CODE. STAIRS, MEZZANINES, AND EGRESS COMPONENTS SHALL
 CONFORM TO THE LIFE SAFETY REQUIREMENTS OF CHAPTER 7 OF
 NFPA 101 FLORIDA 2007 EDITION.
  
 PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH
 EXIT SIGNS.
  
 INDICATE WHAT TYPES OF MATERIALS WILL BE STORED AND HOW
 THE MATERIALS WILL BE STORED (RACK, PALLET, SOLID,
 ETC.). PROVIDE STORAGE LAYOUT PLAN.
  
 PROVIDE BUILDING ADDRESS VISIBLE FROM THE STREET.
 NUMBERS SHALL BE AT LEAST SIX-INCHES IN HEIGHT AND
 SHALL CONTRAST THE BACKGROUND (REFERENCE: SECTION
 10.12.1.2 OF THE FLORIDA FIRE PREVENTION CODE ? NFPA
 1).
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW