| 2011-07-25 12:25:17 | SPECIFY ON THE PLANS HOW THE LIGHTING WILL BE | | | CONTROLLED USING MOTION SENSORS OR SIMILAR TECHNIQUES | | | AS REQUIRED BY THE FLORIDA BUILDING CODE. AUTOMATIC | | | LIGHTING CONTROL FBC 13-415.ABC.1.1; AUTOMATIC SPACE | | | CONTROL FBC 13-415 ABC.1.2; ADDITIONAL CONTROLS | | | 13-412.ABC.1.3 | | | | | | SPECIFY ON THE PLANS WHAT ELECTRICAL SYSTEMS AND | | | DEVICES ARE EXISTING AND WHICH ARE BEING ADDED. PROVIDE | | | A PANEL SCHEDULE SHOWING THE ELECTRICAL CIRCUITS FOR | | | ALL EXISTING AND NEW EQUIPMENT. NEC 215.5 | | | | | | VERIFY THE ELECTRICAL SERVICE AND EQUIPMENT HAS A | | | SUFFICIENT INTERRUPTING RATING FOR THE AVAILABLE FAULT | | | CURRENT. NEC 110.9 | | | | | | ROBERT LECKY | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | |
|