Plan Review Notes
Plan Review Notes For Permit 11060763
Permit Number 11060763
Review Stop E
Sequence Number 1
Notes
Date Text
2011-07-25 12:25:17SPECIFY ON THE PLANS HOW THE LIGHTING WILL BE
 CONTROLLED USING MOTION SENSORS OR SIMILAR TECHNIQUES
 AS REQUIRED BY THE FLORIDA BUILDING CODE. AUTOMATIC
 LIGHTING CONTROL FBC 13-415.ABC.1.1; AUTOMATIC SPACE
 CONTROL FBC 13-415 ABC.1.2; ADDITIONAL CONTROLS
 13-412.ABC.1.3
  
 SPECIFY ON THE PLANS WHAT ELECTRICAL SYSTEMS AND
 DEVICES ARE EXISTING AND WHICH ARE BEING ADDED. PROVIDE
 A PANEL SCHEDULE SHOWING THE ELECTRICAL CIRCUITS FOR
 ALL EXISTING AND NEW EQUIPMENT. NEC 215.5
  
 VERIFY THE ELECTRICAL SERVICE AND EQUIPMENT HAS A
 SUFFICIENT INTERRUPTING RATING FOR THE AVAILABLE FAULT
 CURRENT. NEC 110.9
  