| 2011-07-13 09:15:08 | ELECTRICAL PLAN INSUFFICIENTLY DETAILED TO APPROVE FOR |
| | CONSTRUCTION. PLEASE PROVIDE THE FOLLOWING: |
| | |
| | INDICATE THE SIZE, RATING, VOLTAGE, LOCATION OF THE |
| | EXISTING SERVICE, MAIN DISCONNECTS AND PANELBOARD. |
| | PROVIDE PANEL SCHEDULES AND LOAD CALCULATION. PROVIDE |
| | AN ELECTRICAL RISER DIAGRAM. INCLUDE NEW AND EXISTING |
| | LOADS. NEC 215.5 |
| | PROVIDE DEDICATED 20 AMP BRANCH CIRCUITS AS REQUIRED |
| | FOR BATH ROOM AND KITCHEN AREAS. NEC 210.11 |
| | ADD RECEPTACLES SO THAT NO WALL SPACE IS MORE THAN 6 |
| | FEET FROM A RECEPTACLE AND ALL WALL SPACES MORE THAN 2 |
| | FEET IN WIDTH HAVE A RECEPTACLE. NEC 210.52 |
| | RECEPTACLES ARE REQUIRED IN HALLWAYS. NEC 210.52 (H) |
| | GFCI PROTECTED RECEPTACLES ARE REQUIRED ON THE |
| | BALCONIES. NEC 210.52(E) |
| | ALL GENERAL PURPOSE OUTLETS INCLUDING THOSE IN THE |
| | BEDROOMS AND SMOKE ALARMS MUST BE AFCI PROTECTED. NEC |
| | 210.12(B) |
| | NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11 |
| | AT LEAST ONE WALL SWITCH-CONTROLLED LIGHTING OUTLET IS |
| | REQUIRED IN EVERY HABITABLE ROOM. NEC 210.70 (A)(1). |
| | REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO |
| | INCLUDE INTERCONNECTED SMOKE DETECTORS. IF THE |
| | RESIDENCE HAS GAS APPLIANCES, AN ATTACHED GARAGE OR A |
| | FIRE PLACE A CARBON MONOXIDE DETECTOR IS REQUIRED |
| | WITHIN TEN FEET OF EACH ROOM USED FOR SLEEPING. FBC |
| | R313 |
| | |