| 2011-06-29 14:46:50 | RESIDENTIAL (R3) SHUTTERS INSTALLATION BUILDING REVIEW |
| | CHECKLIST. |
| | 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS. |
| | |
| | 1- ACCORDION SHUTTER SPAN FOR OPENING #12 EXCEEDS THE |
| | MAXIMUM PANEL SPAN OF 13'-0". SEE TABLE 3 ON SHUTTERS |
| | DRAWINGS. PROVIDE PRODUCT APPROVAL THAT ALLOWS THE SPAN |
| | SPECIFIED FOR OPENING #12 AS REQUIRED BY DCA RULE |
| | 9B-72. |
| | |
| | 2- ACCORDING TO TABLE 3 ON SHEET 1 OF 22 OF ACCORDION |
| | SHUTTERS FLORIDA PRODUCT APPROVAL FL10753-R3 SUBMITTED |
| | THE MAXIMUM SHUTTER SPAN IS 142". SHUTTER SPAN FOR |
| | OPENINGS #10, #11, #12 AND #14 NEED TO BE REVISED. |
| | NOTE: TABLE 3 IS BASED ON THE CALCULATED DESIGN |
| | PRESSURES. CONTRACTOR WROTE ON FRONT PAGE OF THE |
| | INSTALLATION SCHEDULE WORST CASE DESIGN PRESSURES OF |
| | 62PSF. THIS WERE THE DESIGN PRESSURES USED TO CHECK THE |
| | MAXIMUM SPAN. |
| | |
| | 3- CLARIFY HOW OPENING #10 COMPLIES WITH THE EGRESS |
| | REQUIREMENTS OF SEC. R310.4. |
| | |
| | 4- DESIGN PRESSURES SUBMITTED FROM ENGINEERING EXPRESS |
| | NEED TO HAVE THE ENGINEER'S ORIGINAL SIGNATURE AND SEAL |
| | AS REQUIRED BY CHAPTER 471 FLORIDA STATUTE. |
| | |
| | 5- COORDINATE INFORMATION SHOWN ON THE SHUTTERS |
| | INSTALLATION WITH ENGINEER CALCULATIONS AND WITH WORST |
| | CASE DESIGN PRESSURES SPECIFIED ON FRONT OF |
| | INSTALLATION SCHEDULE. |
| | |
| | 6- CLEARLY IDENTIFY SPECIFIC ACCORDION SHUTTERS |
| | MOUNTING SECTION AND CONNECTION TYPE. EG: BUILD OUT |
| | MOUNT SECTION CA, WALL MOUNT SECTION D OR DECORATIVE |
| | FLOOR TRACK DETAIL N. ALL OF THEM ARE CIRCLED ON THE |
| | PRODUCT APPROVAL SUBMITTED. NEED TO IDENTIFY SPECIFIC |
| | ONE THAT APPLIES TO THIS JOB TO VERIFY CONNECTION TYPE |
| | SPECIFIED. SEC. 106.1.2 CITY AMENDMENTS TO FBC. |
| | |
| | 7- ANCHOR SPECIFIED ON INSTALLATION SCHEDULE DOESN'T |
| | PROVIDE THE 1 3/4" MIN. EMBEDMENT IN CONCRETE AS |
| | REQUIRED ON THE ANCHOR SCHEDULE FOR CONCRETE. REVISE |
| | THE 2 1/4" ANCHOR SPECIFIED ON THE INSTALLATION |
| | SCHEDULE AND CLEARLY SPECIFY TYPE OF TAPCON. SEE ANCHOR |
| | TABLE FOR CONCRETE. NOTE: EMBEDMENT DOESN'T INCLUDE THE |
| | 5/8" STUCCO FINISH AND THE THICKNESS OF THE SHUTTERS |
| | TRACK. |
| | |