| Plan Review Notes For Permit 11060719 |
| Permit Number |
11060719 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2011-07-26 13:25:15 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2007 | | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | | | 1. SEE SHEET 16 OF THE PRODUCT APPROVAL. PLEASE REVISE | | | INSTALLATION SCHEDULE TO INCLUDE SHUTTER CONNECTION | | | MOUNTING TYPE. THIS SHOULD CORRELATE WITH THE ANCHOR | | | CHARTS (FOR EXAMPLE, M THROUGH X IF THE SUBSTRATE IS | | | WOOD). | | | | | | 2. THE ANCHOR SPACING PROPOSED (12") ON THE | | | INSTALLATION SCHEDULE DOES NOT COMPLY WITH THE | | | REQUIREMENTS OF THE PRODUCT APPROVAL FOR ANY OF THE | | | MOUNTING TYPES FOR WOOD SUBSTRATE. PLEASE REVISE | | | INSTALLATION SCHEDULE. | | | | | | 3. PRIOR TO RESUBMITTAL, PLEASE HAVE THE QUALIFIER | | | REVIEW INSTALLATION SCHEDULE FOR CODE COMPLIANCE. | | | | | | | | | |
|