2011-07-13 13:58:30BUILDING PLAN REVIEW
 PERMIT: 11060701
 ADD: 6424 64TH WAY
 CONT:O/B NACHAICHOTE, PIMDARA
 TEL: (561)542-6673
 2007 FLORIDA BUILDING CODE RESIDENTIAL W/ 2009 FBC
 SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) R 301.2.1.1 PLEASE PROVIDE DESIGN CRITERIA
 CONSTRUCTION IN REGIONS WHERE THE BASIC WIND SPEEDS
 FROM FIGURE R301.2(4) EQUAL OR EXCEED 100 MILES PER
 HOUR (45 M/S) SHALL BE PERMITTED TO BE DESIGNED IN
 ACCORDANCE WITH ONE OF THE FOLLOWING:
  
 1.1. AMERICAN FOREST AND PAPER ASSOCIATION (AF&PA) WOOD
 FRAME CONSTRUCTION MANUAL FOR ONE- AND TWO-FAMILY
 DWELLINGS (WFCM);
  
 1.2. MINIMUM DESIGN LOADS FOR BUILDINGS AND OTHER
 STRUCTURES (ASCE-7);
  
 1.3. AMERICAN IRON AND STEEL INSTITUTE (AISI), STANDARD
 FOR COLD-FORMED STEEL FRAMING?PRESCRIPTIVE METHOD FOR
 ONE- AND TWO-FAMILY DWELLINGS (COFS/PM) WITH SUPPLEMENT
 TO STANDARD FOR COLD-FORMED STEEL FRAMING?PRESCRIPTIVE
 METHOD FOR ONE- AND TWO-FAMILY DWELLINGS.
  
 1.4. CONCRETE AND CONCRETE MASONRY CONSTRUCTION SHALL
 BE DESIGNED IN ACCORDANCE WITH THE PROVISIONS OF THIS
 CODE OR IN ACCORDANCE WITH THE APPLICABLE DOCUMENTS
 ADOPTED IN SECTION R301.2.1.1.
  
 1. 5. IBHS GUIDELINE FOR HURRICANE RESISTANT
 RESIDENTIAL CONSTRUCTION SHALL BE PERMITTED FOR
 BUILDINGS FOR A BASIC WIND SPEED OF 140 MPH (63 M/S) OR
 LESS IN EXPOSURE B IN ACCORDANCE WITH FIGURE R301.2(4).
 PROVISIONS FOR DESIGN WIND SPEEDS OF 140 MPH (63 M/S)
 IN THE GUIDELINE SHALL ALSO BE PERMITTED FOR BUILDINGS
 FOR A BASIC WIND SPEED OF 120 MPH (54 M/S) OR LESS IN
 EXPOSURE C IN ACCORDANCE WITH FIGURE R301.2(4) AND
 PROVISIONS FOR DESIGN WIND SPEEDS OF 120 MPH (54 M/S)
 IN THE GUIDELINE SHALL BE PERMITTED FOR BUILDINGS FOR A
 BASIC WIND SPEED OF 100 MPH (45 M/S) OR LESS IN
 EXPOSURE C IN ACCORDANCE WITH FIGURE R301.2(4).
  
 1.6. THE FC&PA GUIDE TO CONCRETE MASONRY RESIDENTIAL
 CONSTRUCTION IN HIGH WIND AREAS SHALL BE PERMITTED FOR
 APPLICABLE CONCRETE MASONRY BUILDINGS FOR A BASIC WIND
 SPEED OF 130 MPH (58 M/S) OR LESS IN EXPOSURE B AND 110
 MPH (49 M/S) OR LESS IN EXPOSURE C IN ACCORDANCE WITH
 FIGURE R301.2(4);
  
 1.7. THE WPPC GUIDE TO WOOD CONSTRUCTION IN HIGH WIND
 AREAS SHALL BE PERMITTED FOR APPLICABLE WOOD-FRAME
 BUILDINGS FOR A BASIC WIND SPEED OF 130 MPH (58 M/S) OR
 LESS IN EXPOSURE B AND 110 MPH (49 M/S) OR LESS IN
 EXPOSURE C IN ACCORDANCE WITH FIGURE R301.2(4); OR.
  
 1.8. THE FLORIDA BUILDING CODE, BUILDING.
  
 2) PLEASE PROVIDE THE WIND DESIGN CRITERIA PER
 R301.2.1.5
 2.1) THE BASIC WIND SPEED, V, SHALL BE DETERMINED IN
 ACCORDANCE WITH SECTION 1609.3. THE WIND SHALL BE
 ASSUMED TO COME FROM ANY HORIZONTAL DIRECTION.
  
 2.2) AN IMPORTANCE FACTOR, IW, SHALL BE DETERMINED IN
 ACCORDANCE WITH SECTION1609.5.
  
 2.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4.
  
 2.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.6.2.1(4)
  
  
 3) PLANS SHOW INCONSISTENCIES:
  
 3.1) ON THE FRONT SHEET THE VERTICAL SUPPORTS APPEAR TO
 BE BURIED INTO THE GROUND WITH FOUNDATIONS, BUT OTHER
 SHEETS SHOW A BOTTOM COLUMN BASE THAT APPEARS TO BE
 ANCHORED TO SOME OBJECT POSSIBLE CONCRETE, NOT
 INDICATED. THE VERTICAL LENGTH OF THE 4X4 IS INDICATED
 AS 132 INCHES. PLEASE CLARIFY THESE
 DISCREPANCIES. IDENTIFY THE POST BY SPECIES & GRADE OF
 WOOD, IF NATURALLY DURABLE OR WOOD THAT IS PRESERVATIVE
 TREATED IN ACCORDANCE WITH AWPA U1 FOR THE SPECIES,
 PRODUCT, PRESERVATIVE AND END USE. PRESERVATIVES SHALL
 BE LISTED IN SECTION 4 OF AWPA U1.
 R319.1.2 GROUND CONTACT. ALL WOOD IN CONTACT WITH THE
 GROUND, EMBEDDED IN CONCRETE IN DIRECT CONTACT WITH THE
 GROUND OR EMBEDDED IN CONCRETE EXPOSED TO THE WEATHER
 THAT SUPPORTS PERMANENT STRUCTURES INTENDED FOR HUMAN
 OCCUPANCY SHALL BE APPROVED
 PRESSURE-PRESERVATIVE-TREATED WOOD SUITABLE FOR GROUND
 CONTACT USE, EXCEPT UNTREATED WOOD MAY BE USED WHERE
 ENTIRELY BELOW GROUNDWATER LEVEL OR CONTINUOUSLY
 SUBMERGED IN FRESH WATER.
  
 3.2 THE FRONT PLAN INDICATES CENTER LINE TO CENTER LINE
 A SHADE STURTURE THAT IS 12 FEET BY 13 FEET BUT WHEN
 YOU TOTAL UP TTHE SPACES BETWEEN POST THERE IS A
 DISCREPANCY IN DIMINSIONS PLEASE CORRECT.
  
 4) DETAILS DO SHOW THE USE OF A BOTTOM COLUMN BASE
 PLEASE PROVIDE THE MANUFACTRER, MODEL NUMBER AND TYPE
 OF ANCHORS TO INSTALL THE COLUMN BASE TO ASSUMED
 CONCRETE, NOT BRICK PAVERS AND THE TYPE OF ANCHOR TO BE
 USED TO TIE THE POST TO THE BOTTOM COLUMN BASE. PROVIDE
 ANCHOR INFORMATION AS WELL.
  
 5) THE PLANS SHOW A DOUBLE 2X6 AS THE CARRYING BEAMS
 PLEASE IDENTIFY THE TYPE OF ANCHORS TO BE USED TO
 ANCHOR THE CARRYING (2) 2X6 MEMBERS TO THE 4 VERTICAL
 POST.
  
 6) PLEASE PROVIDE AN ANALYSIS AS TO THE (2) 2X6
 CARRYING MEMBERS BEING ABLE TO CARRY HALF OF THE 12
 FOOT SPAN PLUS THE TAILS AND THE ADDITIONAL LOADING OF
 2X6'S PLACED AT 90 DEGREES? 2007/09 FBC-R TABLE
 R502.2.5(2)
  
 THE PLANS DO NOT PROVIDE HOW THE 2X6 FRAMING MEMBERS
 ARE GOING TO BE SECURED TO THTE 2X6 CARRYING MEMBERS?
 NOTE THIS DESIGN IS TO BE FOR 140 MPH 3 SECOND GUST
 WIND LOADS, EXPOSURE "C".
  
 JAMES A. WITMER
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER