| 2011-06-29 09:13:33 | RESIDENTIAL (R3) ALTERATION BUILDING REVIEW CHECKLIST. | | | 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS. | | | | | | 1- WINDOW NOA 10-0308.02 SUBMITTED DOESN'T INCLUDE THE | | | WINDOW SIZE SPECIFIED ON PLANS. PROVIDE PRODUCT | | | APPROVAL (2 COPIES) FOR WINDOWS SIZE AS SPECIFIED ON | | | ARCHITECT'S PLANS AS REQUIRED BY DCA RULE 9N-3. | | | | | | 2- ARCHITECT OF RECORD TO REVIEW AND APPROVE IN WRITING | | | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS | | | REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC. | | | | | | 3- STRUCTURAL WINDOW JAMB DETAIL ON SHEET A-1: | | | A) ARCHITECT TO SPECIFY BUCK ANCHOR SPACING. SEC. | | | 106.1.2 CITY AMENDMENTS TO FBC. | | | | | | B) WINDOW BUCK SHALL PROVIDE FULL SUPPORT TO THE WINDOW | | | FRAME AS REQUIRED BY SEC. R613.6.1.1. REVISE SIZE OF | | | BUCK TO PROVIDE WINDOW FRAME FULL SUPPORT. SEE WINDOW | | | PRODUCT APPROVAL FOR WIDTH SIZE OF WINDOW FRAME AND | | | REVISE AS REQUIRED. | | | | | | 4- ARCHITECT TO UPDATE CODE EDITION SPECIFIED ON THE | | | DESIGN CERTIFICATION FOR WIND LOAD COMPLIANCE TABLE ON | | | SHEET A-1. 2007 FLORIDA RESIDENTIAL CODE ADOPTED ASCE 7 | | | -05 EDITION NOT ASCE 7-02. REVISE AS REQUIRED. | | | | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 |
|