2011-06-29 09:13:33RESIDENTIAL (R3) ALTERATION BUILDING REVIEW CHECKLIST.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- WINDOW NOA 10-0308.02 SUBMITTED DOESN'T INCLUDE THE
 WINDOW SIZE SPECIFIED ON PLANS. PROVIDE PRODUCT
 APPROVAL (2 COPIES) FOR WINDOWS SIZE AS SPECIFIED ON
 ARCHITECT'S PLANS AS REQUIRED BY DCA RULE 9N-3.
  
 2- ARCHITECT OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC.
  
 3- STRUCTURAL WINDOW JAMB DETAIL ON SHEET A-1:
 A) ARCHITECT TO SPECIFY BUCK ANCHOR SPACING. SEC.
 106.1.2 CITY AMENDMENTS TO FBC.
  
 B) WINDOW BUCK SHALL PROVIDE FULL SUPPORT TO THE WINDOW
 FRAME AS REQUIRED BY SEC. R613.6.1.1. REVISE SIZE OF
 BUCK TO PROVIDE WINDOW FRAME FULL SUPPORT. SEE WINDOW
 PRODUCT APPROVAL FOR WIDTH SIZE OF WINDOW FRAME AND
 REVISE AS REQUIRED.
  
 4- ARCHITECT TO UPDATE CODE EDITION SPECIFIED ON THE
 DESIGN CERTIFICATION FOR WIND LOAD COMPLIANCE TABLE ON
 SHEET A-1. 2007 FLORIDA RESIDENTIAL CODE ADOPTED ASCE 7
 -05 EDITION NOT ASCE 7-02. REVISE AS REQUIRED.
  