| Plan Review Notes For Permit 11060668 |
| Permit Number |
11060668 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-06-29 14:24:14 | ****CORRECTIONS**** | | | | | | 1. THE PLAN IS DIFFICULT TO READ. PLEASE PROVIDE A | | | LEGIBLE PLAN WHICH SHOWS ALL PROPOSED DUCT SIZES. FBC | | | RESIDENTIAL 1601. | | | | | | 2. PROVIDE AN ANCHORING DETAIL FOR THE PROPOSED | | | CONDENSING UNIT, FBC RESIDENTIAL M1307.3. | | | | | | 3. PROVIDE A SITE PLAN WHICH SHOWS PROPOSED LOCATION OF | | | CONDENSING UNIT, FBC106. | | | | | | HAROLD MOSER, MECHANICAL PLANS EXAMINER | | | 561-805-6724 | | | | | | |
|