Plan Review Notes
Plan Review Notes For Permit 11060648
Permit Number 11060648
Review Stop E
Sequence Number 1
Notes
Date Text
2011-07-05 12:05:48 
 PROVIDE ELECTRICAL RISER PLAN SHOWING OVERHEAD SERVICE,
 CONDUIT, WIRE AND GROUNDING.
 RECEPTACLES IN KITCHEN AREAS SHALL BE GFCI PROTECTED.
 NEC 210.8
 REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO
 INCLUDE INTERCONNECTED SMOKE DETECTORS WITH BATTER BACK
 UP. HOMES WHICH FEATURE GAS APPLIANCES, AN ATTACHED
 GARAGE OR A FIRE PLACE REQUIRE A CARBON MONOXIDE
 DETECTOR WITHIN TEN FEET OF EACH ROOM USED FOR
 SLEEPING. FBC R313
 PROVIDE AN INTERSYSTEM BONDING STRIP AT THE SERVICE
 GROUND. NEC 250.94
 RECEPTACLES MUST BE ARC FAULT CIRCUIT PROTECTED AND
 TAMPER RESISTANT. NEC 406.11, NEC 210-12 (B)
 A GFCI PROTECTED RECEPTACLE IS REQUIRED AT MAIN
 ENTRANCE. NEC 210.52
  
  
 ROBERT LECKY
 COMMERCIAL COMBINATION PLANS EXAMINER
 [email protected]
 561-805-6718
  
  
  