| Plan Review Notes For Permit 11060648 |
| Permit Number |
11060648 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-07-05 12:05:48 | | | | PROVIDE ELECTRICAL RISER PLAN SHOWING OVERHEAD SERVICE, | | | CONDUIT, WIRE AND GROUNDING. | | | RECEPTACLES IN KITCHEN AREAS SHALL BE GFCI PROTECTED. | | | NEC 210.8 | | | REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO | | | INCLUDE INTERCONNECTED SMOKE DETECTORS WITH BATTER BACK | | | UP. HOMES WHICH FEATURE GAS APPLIANCES, AN ATTACHED | | | GARAGE OR A FIRE PLACE REQUIRE A CARBON MONOXIDE | | | DETECTOR WITHIN TEN FEET OF EACH ROOM USED FOR | | | SLEEPING. FBC R313 | | | PROVIDE AN INTERSYSTEM BONDING STRIP AT THE SERVICE | | | GROUND. NEC 250.94 | | | RECEPTACLES MUST BE ARC FAULT CIRCUIT PROTECTED AND | | | TAMPER RESISTANT. NEC 406.11, NEC 210-12 (B) | | | A GFCI PROTECTED RECEPTACLE IS REQUIRED AT MAIN | | | ENTRANCE. NEC 210.52 | | | | | | | | | ROBERT LECKY | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | | | | | | | | | 2011-06-24 15:41:44 | UNDER 5 K ELECTRIC |
|