| 2011-07-05 11:03:36 | 477 SOUTH ROSEMARY AVENUE, SUITE #221 |
| | PERMIT #11060593 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | DESIGN SHALL CONFORM TO THE FLORIDA FIRE PREVENTION |
| | CODE 2007 EDITION: NFPA 1 AND NFPA 101 - 2006 EDITION |
| | WITH FLORIDA AMENDMENTS. |
| | |
| | PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS |
| | SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE |
| | TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL |
| | DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET. |
| | |
| | PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH |
| | EXIT SIGNS. |
| | |
| | PROVIDE A LIFE SAFETY PLAN INDICATING LOCATION OF FIRE |
| | RATED WALLS AND DOORS, PATH OF TRAVEL TO EXITS, ETC. |
| | |
| | DURING ITS SWING, ANY DOOR IN A MEANS OF EGRESS SHALL |
| | NOT PROJECT MORE THAN 7-INCHES INTO THE REQUIRED WIDTH |
| | OF A HALLWAY, CORRIDOR OR PASSAGEWAY. THREE OFFICE |
| | DOORS AND ONE RESTROOM DOOR OBSTRUCT EGREES. |
| | |
| | NO SCOPE OF WORK PROVIDED FOR THE CONTRACTORS REGARDING |
| | THE INSTALLATION/MODIFICATION OF THE FIRE SPRINKLER AND |
| | FIRE ALARM SYSTEM. INDICATE SYSTEM TYPES, OCCUPANCY |
| | HAZARD CLASSIFICATIONS, DESIGN DENSITIES, SYSTEM |
| | CONTROL VALVES, AUDIBLE/VISUAL NOTIFICATION APPLIANCE |
| | LOCATIONS AND INITIATING DEVICE LOCATIONS. NOTE: THE |
| | FIRE SPRINKLERS PROTECTING THIS SPACE MAY BE |
| | RESIDENTIAL TYPE SPRINKLERS. RESIDENTIAL SPRINKLERS |
| | WOULD NEED TO BE REPLACED WITH COMMERCIAL TYPE |
| | SPRINKLERS. |
| | |
| | PER FLORIDA ADMINISTRATIVE CODE SECTION 61G15-32.004, |
| | PLANS SHALL INDICATE THE HAZARD CLASSIFICATIONS, DESIGN |
| | DENSITIES, AND HYDRANT FLOW TEST DATA. |
| | |
| | PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY |
| | RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING |
| | NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM |
| | WWW.KNOXBOX.COM. |
| | |
| | WESLEY JOLIN |
| | WEST PALM BEACH FIRE RESCUE |
| | FIRE & LIFE SAFETY PLAN REVIEW |
| | |