2011-07-05 11:03:36477 SOUTH ROSEMARY AVENUE, SUITE #221
 PERMIT #11060593
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 DESIGN SHALL CONFORM TO THE FLORIDA FIRE PREVENTION
 CODE 2007 EDITION: NFPA 1 AND NFPA 101 - 2006 EDITION
 WITH FLORIDA AMENDMENTS.
  
 PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
  
 PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH
 EXIT SIGNS.
  
 PROVIDE A LIFE SAFETY PLAN INDICATING LOCATION OF FIRE
 RATED WALLS AND DOORS, PATH OF TRAVEL TO EXITS, ETC.
  
 DURING ITS SWING, ANY DOOR IN A MEANS OF EGRESS SHALL
 NOT PROJECT MORE THAN 7-INCHES INTO THE REQUIRED WIDTH
 OF A HALLWAY, CORRIDOR OR PASSAGEWAY. THREE OFFICE
 DOORS AND ONE RESTROOM DOOR OBSTRUCT EGREES.
  
 NO SCOPE OF WORK PROVIDED FOR THE CONTRACTORS REGARDING
 THE INSTALLATION/MODIFICATION OF THE FIRE SPRINKLER AND
 FIRE ALARM SYSTEM. INDICATE SYSTEM TYPES, OCCUPANCY
 HAZARD CLASSIFICATIONS, DESIGN DENSITIES, SYSTEM
 CONTROL VALVES, AUDIBLE/VISUAL NOTIFICATION APPLIANCE
 LOCATIONS AND INITIATING DEVICE LOCATIONS. NOTE: THE
 FIRE SPRINKLERS PROTECTING THIS SPACE MAY BE
 RESIDENTIAL TYPE SPRINKLERS. RESIDENTIAL SPRINKLERS
 WOULD NEED TO BE REPLACED WITH COMMERCIAL TYPE
 SPRINKLERS.
  
 PER FLORIDA ADMINISTRATIVE CODE SECTION 61G15-32.004,
 PLANS SHALL INDICATE THE HAZARD CLASSIFICATIONS, DESIGN
 DENSITIES, AND HYDRANT FLOW TEST DATA.
  
 PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY
 RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING
 NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM
 WWW.KNOXBOX.COM.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  